Installation manual
23
RKHBRD011~Y1
Indoor unit for air to water heat pump system
4PW61218-1C – 2012.06
■
[3-00]
Low ambient temperature (Lo_A): low outdoor
temperature.
■
[3-01]
High ambient temperature (Hi_A): high outdoor
temperature.
■
[3-02]
Set point at low ambient temperature (Lo_Ti): the target
outgoing water temperature when the outdoor temperature
equals or drops below the low ambient temperature (Lo_A).
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is required.
■
[3-03]
Set point at high ambient temperature (Hi_Ti): the target
outgoing water temperature when the outdoor temperature
equals or rises above the high ambient temperature (Hi_A).
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water suffices.
[4] Disinfection function
This mode will disinfect the domestic hot water tank by periodically
heating the domestic water to a specific temperature.
■
[4-00]
Status: defines whether the disinfection function is turned
ON (1) or OFF (0).
■
[4-01]
Operation interval: day of the week at which the domestic
water should be heated.
■
[4-02]
Start time: time at which the disinfection operation is
started
Even if all schedule timers are de-activated and there is no reheat
function active, the disinfection function will operate if a domestic hot
water tank is installed and field setting [4-00] is set to ON.
Refer to "[5]
Automatic setback and disinfection set point" for
temperature set points.
[5] Automatic setback and disinfection set point
See also "[4] Disinfection function" on page 23 for more information
about the disinfection operation.
■
[5-00]
Set point: disinfection water temperature to be reached
■
[5-01]
Interval: time period defining how long the disinfection
temperature set point should be maintained
See also "[2] Automatic setback function" on page 22 for more
information about the setback operation.
■
[5-02]
Leaving water setback temperature
■
[5-03]
Room setback temperature
[6] Option setup
■
[6-00]
Domestic hot water tank option
If the domestic hot water tank is installed, its operation must be
enabled by field setting. Default [6-00]=0 which means no tank is
installed. Set [6-00] to 1 if the optional domestic hot water tank is
installed.
■
[6-01]
External room thermostat option
If the optional external room thermostat is installed, its operation
must be enabled by field setting. Default [6-01]=0, which means
no external room thermostat is installed. Set [6-01] to 1 if the
optional external room thermostat is installed.
The external room thermostat only gives an ON/OFF signal to
the heat pump based on the room temperature. Because it does
not give continuous feedback information to the heat pump, it is
supplementary to the remote controller room thermostat
function. To have a good control of the system and avoiding
frequent ON/OFF it is advised to use the automatic weather
dependent set point operation.
■
[6-02]
Heater kit
Once installed, you can activate the heater kit by changing field
setting [6-02]=1.
From that moment on, the heat pump system will take the heater
kit into account whilst deciding operation. When the heater is
actually operating, the heater symbol
is shown on the remote
controller. There is no step 1-2 indication.
For more information, see installation manual of the heater kit,
especially concerning the test run for the heater kit.
■
[6-03]
Solar support
For more information refer to the EKHWP installation manual.
■
[6-04]
Benefit kWh rate power supply mode
If benefit kWh rate power supply is used, the mode must be
selected. Default [6-04]=0 which means no benefit kWh rate
power supply is used.
Set [6-04] to 1 to use benefit kWh rate power supply mode 1
(normally closed contact which will open when the power supply
is interrupted), or set [6-04] to 2 to use benefit kWh rate power
supply mode 2 (normally opened contact which will close when
the power supply is interrupted).
See "Connection to a benefit kWh rate power supply" on page 17 for
more information.
[7] Option setup
■
[7-00]
Bottom plate heater option
An optional bottom plate heater can be installed in your outdoor
unit. In case an RRRQ* outdoor unit (special model with freeze-
up countermeasures) is installed, the unit will have the bottom
plate heater already standard installed.
If the bottom plate heater is installed, its operation must be
enabled by field setting. Default [7-00]=1 which means the
bottom plate heater is installed. Set [7-00] to 0 if no bottom plate
heater is installed.
■
[7-02]
See chapter "Multiple set point control" on page 29
■
[7-03]
See chapter "Multiple set point control" on page 29
■
[7-04]
See chapter "Multiple set point control" on page 29
NOTE
If by mistake the value of [3-03] is set higher than the
value of [3-02], the value of [3-03] will always be used.
NOTE
If a domestic hot water tank is installed, the disinfection
function is enabled by default.
The disinfection function field settings must be configured
by the installer according to national and local regulations.
A
Storage operation (if activated)
B
Reheat operation (if activated)
C
Disinfection operation (if activated)
Field settings
D
Disinfection operation temperature [5-00] (e.g. 70°C)
E
Hot water storage temperature [b-03] (e.g. 60°C)
F
Reheat maximum water temperature [b-01] (e.g. 45°C)
G
Reheat minimum water temperature [b-00] (e.g. 35°C)
t
Time
T
Domestic hot water tank temperature
A
B
C
D
E
F
G
T
t
[5-01]
NOTE
When enabling the domestic hot water tank option
be aware that the advised default settings become
active:
■
[1-00]=
1=automatic night storage
■
[4-00]=
1=disinfection function