6 ROTEX control system ALPHA
+
23R
40
FA ROTEX ESU - 07/2008
6.5.7 Manual operation
– The heat generator is controlled in accordance with the set target value. It is only limited by the maximum heat generator
temperature (parameter [12]).
– All pumps are operational.
– Any mixers are disconnected and can be controlled manually in accordance with a heat request.
– The hot water is maintained at the absolute minimum temperature (15 °C) and takes precedence over heating mode.
– The burner request is made using the heat generator's standard switching hysteresis.
– If the rotary switch "operating mode selection" is set to "summer" when activating manual operation, the constant
temperature is applied to the storage tank otherwise to the heating system. It is not possible to switch between the heating
system and the storage tank when manual operation is active.
– The adjustable target temperature is represented by a following "H" and changes with the actual flow temperature.
6.5.8 Querying system information
1.
Set the "Default settings" rotary switch to position
and press
the
and
keys simultaneously, holding them down for longer
than 5 s.
Î
Manual operation is activated.
2.
Use the
and
keys to
set the required target temperature.
3.
Press the
and
keys simultaneously.
Î
Exits the programme.
Fig. 6-11 Activate and set manual operation
Info values relating to functions, which have not been activated are not shown.
Certain info values are blocked from the display. The installer can call these values up by entering an access
code (see section 6.6.4).
1.
Set the "Default settings" rotary switch to position
.
Î
The word "INFO" appears on the display for a few seconds,
then left-aligned the info value number and right-aligned the
corresponding info value are alternately displayed.
2.
You can use the
and
keys to select and display the required
information (see Table 6-5 to Table 6-6).
3.
Exit system information by setting the "Default settings" rotary switch
to a different position.
Fig. 6-12 Querying system information
38
38
45 H
55 H
+
Soll
Ist
EXIT
5 sec
i
i
InFo
I
21