EbV
Product documentation THETA NORM/UNIT
8-50
Start-up protection:
Buffer start-up protection (only with charging control)
In buffer operation there is no start-up protection for the heat generator acting on the
heating circuits. The start-up protection only acts on the buffer loading pump. When
buffer start-up protection is switched on and the buffer tank temperature drops below
the minimum temperature limit, all consumer circuits are separated hydraulically
(pumps are switched off). The buffer start-up protection is disabled (pumps are
switched on again) when the buffer tank temperature exceeds the buffer minimum
temperature plus half of he buffer switching differential. All consumer circuits remain
in operation when buffer start-up protection is switched off.
Discharge
protection:
Buffer discharge protection (only charging control)
Buffer discharge protection disables the buffer loading pump until the heat generator
temperature has risen to more than 5 K above the buffer nominal temperature.
This measure prevents any rear buffer discharge through the heat generator. The
buffer loading pump is disabled again as soon as the temperature difference
between the heat generator and the buffer tank has dropped to less than 2 K.
Buffer sensor 2:
Buffer sensor 2 (BU 2)
The buffer tank can be equipped with a second sensor (BU2) for unmixed storage
tank loading and discharge. Loading starts if the highest of both temperatures falls
below the setpoint. Loading is finished if the lowest of both temperatures exceeds the
setpoint plus buffer switching differential. [stratified discharge]
Operation buffer parameters:
Note on operation
Key / parameter tree
Parameter
Buffer sensor 2 (bottom)
HYDRAULIC
PARAMETER 08
or
PARAMETER 09
or
PARAMETER 10
Minimum temperature
BUFFER
PARAMETER 01
Maximum temperature
BUFFER
PARAMETER 02
Temperature excess H-GEN
BUFFER
PARAMETER 03
Switching differential
BUFFER
PARAMETER 04
Forced heat dissipation
BUFFER
PARAMETER 05
Drain function switch-on differential
BUFFER
PARAMETER 06
Drain function switch-off differential
BUFFER
PARAMETER 07
Start-up protection
BUFFER
PARAMETER 08
Discharge protection
BUFFER
PARAMETER 09
Содержание Controller Series
Страница 2: ......
Страница 8: ...EbV Product documentation THETA NORM UNIT VI...
Страница 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Страница 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Страница 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Страница 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Страница 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Страница 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Страница 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Страница 170: ...EbV Product documentation THETA NORM UNIT 11 8...
Страница 192: ...PD_THETA NURS_EbV_GB_0460017001_0612 23...