Product documentation THETA NORM/UNIT
8-38
Note:
The heat generator minimum temperature limit operates continuously to protect the
heat generator and blocks the DHW loading pump in case of temperatures below the
set value.
CAUTION
In case of DHW temperature settings above 60°C this function should not be
activated to avoid safety switch-off (in particular for heat generators with a low water
capacity).
Boiler Temperature
parallel shift:
Boiler Temperature parallel shift
This function determines the default setting of the tank loading temperature
compared to the set DHW setpoint.
In case of several controllers connected via bus and several DHW circuits the tank
loading temperature depends on the highest setpoint if several tanks are loaded
simultaneously.
Switching differential:
DHW Tank Switching Differential
This function determines the size of the DHW switching differential. The switching
differential affects the relevant DHW setpoint symmetrically.
Loading enabling:
The current DHW temperature is lower than the DHW setpoint by half the amount of
the DHW switching differential.
Loading abort:
The current DHW temperature exceeds the DHW setpoint by half the amount of the
DHW switching differential.
Extended Pump
running time:
DHW-loading pump extended running time
After switching off the heat generator the tank loading pump is stopped only after a
time delay to prevent a safety switch-off in case of high temperatures. The setting
can be adjusted to the capacity of the DHW tank.
Note:
Excessively long overtravel times interrupt unnecessarily the heating mode and
increase the temperature in the hot water tank.
Operation:
Note on operation
Key / parameter tree
Parameter
Activation tank discharge protection
DOMESTIC HOT WATER
PARAMETER 08
Operation:
Note on operation
Key / parameter tree
Parameter
Setting boiler temperature
parallel shift
DOMESTIC HOT WATER
PARAMETER 09
Operation:
Note on operation
Key / parameter tree
Parameter
Setting switching difference
DOMESTIC HOT WATER
PARAMETER 10
Operation:
Note on operation
Key / parameter tree
Parameter
Setting loading pump extended
running time
DOMESTIC HOT WATER
PARAMETER 11
Содержание Controller Series
Страница 2: ......
Страница 8: ...EbV Product documentation THETA NORM UNIT VI...
Страница 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Страница 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Страница 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Страница 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Страница 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Страница 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Страница 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Страница 170: ...EbV Product documentation THETA NORM UNIT 11 8...
Страница 192: ...PD_THETA NURS_EbV_GB_0460017001_0612 23...