EbV
Product documentation THETA NORM/UNIT
8-20
CAUTION
In order to measure the room temperature the heating circuit of the most occupied
room is to be used.
Radiator thermostats are used together with correctly designed radiators to control
the external heat gain and should hence be almost completely open. During the
adjustment phase additional external heat sources like fireplaces, majolica stoves,
etc. should not be used. Furthermore, during the measurement period excessive
ventilation is to be avoided.
The measurement period covers basically the heating phases. If the heating
characteristic is correctly set, the room temperature remains constant according to
the set daytime setpoint regardless of the changes in the outside temperature.
NOTE:
The heating characteristics are limited by the minimum and maximum temperature
limits. With activated limits the relevant flow temperature is controlled exclusively
according to the set limit values.
Operation:
Note on operation
Key / parameter tree
Parameter
Setting Heating curve slope
£
.
Boiler
/f
low t
e
m
p
era
ture
(
°C)
T
Roo
m
(°C)
Outdoor temperature (°C)
Содержание Controller Series
Страница 2: ......
Страница 8: ...EbV Product documentation THETA NORM UNIT VI...
Страница 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Страница 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Страница 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Страница 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Страница 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Страница 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Страница 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Страница 170: ...EbV Product documentation THETA NORM UNIT 11 8...
Страница 192: ...PD_THETA NURS_EbV_GB_0460017001_0612 23...