41
Communicator
|
3.05
10.3.2
Disabling Alarms
•
Go to
ALARM > Disabled Alarms
View disabled alarms and re-enable these alarms.
NOTE:
: Alarms are disabled until 12:00 PM the following day.
•
Scroll right to view message.
•
Press +/- to re-enable the alarm and then press ENTER.
NOTE:
Alarms that are re-enabled are cleared from the list.
10.3.3
Defining the Message Delay
•
Go to
ALARM > Options
.
This menu defines the waiting times between an alarm event and its reporting.
•
CALL-OUT (seconds):
Define the waiting time before the communicator begins the reporting
sequence.
•
BETWEEN USERS (seconds)
: Define the waiting time before contacting the next user within
the address book.
10.3.4
Defining the Message Repeat Parameter
•
Go to
ALARM > Options.
By default, when an alarm is sent, it must be acknowledged by one of the contacts. If there is no
acknowledgment, Communicator resends the alarm (refer to Acknowledging a Message, page 24). This
menu defines the waiting time before Communicator reinitiates the reporting (VOICE, PAGER, TEXT).
NOTE:
Enter 0 to disable this option.
DISABLE ALARMS
DISABLE ALARMS
HOUSE DISABLE CODE
MESSAGE
23
YES
185
25
YES
155
TEXT
==MESSAGE REPEAT==
Voice
20
Pager
35
Text
35
===INTERNAL ALARM===
Delay(s)
60
Reminder (m)
60
Power Resto.Msg
NO
OPTIONS
==MESSAGE DELAY===
Call Out (s)
60
Between Users (s)
60