31
Communicator
|
3.05
Figure 5: Connecting the External Connection box to Controllers via RS-485 Cards
•
The cable between the external connection box and the controllers should be a 2-wire
shielded cable.
•
This cable is daisy-chained to all controllers and to exrternal connection box:
o
Connect the shield to the COM terminal of the controller on one side and leave
unconnected on the other side.
o
Red wire to terminal A of the controller and terminal A of the external connection box.
o
Green wire to terminal B of the controller and terminal B of the external connection
box.
1: Controller communicator card
2: Next house
3: To prevent ground loops, connect the shield
wire at one end only
4: Communicator External Box