Wiring Specifications

Refer  to  the  following  steps  for  details  on  power  and
accessory wiring for the operator.

USE COPPER WIRE ONLY!

AC Power Wiring

1. Connect  power  in  accordance  with  local  codes.  The  green

ground wire must be properly connected.

2. Wire insulation must be suitable to the application.
3. Electrical  outlets  are  supplied  in  all  models  for  convenience

with occasional use or low power consumption devices only.

DC Control and Accessory Wiring

1. All control devices are 24 VDC, which can be run up to 2000

feet with 14 AWG wire.

2. Control wiring must be run in a separate conduit from power

wiring.  Running  them  together  may  cause  interference  and
faulty signals in some accessories

3. A three-wire shielded conductor cable is required to connect

two  operators  together  for  dual  operation. You  must  use
Beldon  8760  Twisted  Pair  shielded  Cable  (or  equivalent)
only  (P/N  2500-1982,  per  foot).  See  Page  21  for  details  of
this connection.

Note:  The  shield  wire  should  be  connected  in  both  the
operators.

Earth Ground

Install a ground rod and connect it to the operator’s control box
in  every  gate  operator  installation.  A  good  earth  ground  is
necessary  to  allow  the  controller’s  built -in  surge  and  lightning
protection circuitry to work effectively.

All  ROTARY  GATE  SYSTEMS  gate  operators  are  supplied
with  a  power  disconnect  switch  to  turn  on  and  off  the  power
available  to  the  operators.  Following  wiring  specifications
below, incoming power should be brought into the operator and
connected to the appropriate wires from the disconnect box.

*NOTE:

Do  not  splice  the  ground  wire.  Use  a  single  piece  of

solid  copper  12  AWG  wire  between  the  ground  rod  and  the
operator.

1. Install an 8-foot long copper ground or nest to the operator

control box.

2. Use  a  clamp  to  connect  a  solid  copper  12  AWG  ground

wire to the ground rod.

3. Route the ground wire to the operator control box.
4. Connect the ground wire to the operator’s control box.

WARNING

ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE
AND  THE  OPERATOR  MUST  BE  MADE  BY  A  LICENSED
ELECTRICIAN  AND  MUST  OBSERVE  ALL  NATIONAL  AND
LOCAL ELECTRICAL CODES.

WARNING

The  gate  must  be  installed  in  a  location  so  that  enough
clearance  is  supplied  between  the  gate  and  adjacent
structures  when  opening  and  closing  to  reduce  the  risk  of
entrapment. Swing gates shall not open into public areas.

BLACK

  HOT

WHITE

  NEUTRAL

GREEN

  GROUND

110 VOLT
OPERATOR
POWER
DISCONNECT
BOX

Содержание SL-1000 R

Страница 1: ...1 SL 1000 R RESIDENTIAL LIGHT COMMERCIAL SLIDE GATE OPERATOR MADE IN U S A ROTARY GATE SYSTEMS INC ALL RIGHTS RESERVED 2008 REV 1 1 1 877 331 4RGS 4747...

Страница 2: ...t reversing Sensor Easy troubleshooting with easy to interpret LED display 200 cycles per day when used on properly installed gates Input for non contact secondary entrapment protection device In addi...

Страница 3: ...t setup Stagger mode Stagger delay time Auxiliary relay mode Reverse delay time Low power mode Power failure mode Soft start stop duration Reset cycle count Maintenance alert trigger Mid travel stop p...

Страница 4: ...ecurity personnel Approved Obstruction Detection Devices The following contact or non contact obstruction detection devices have been approved for use with this slide gate operator as part of a UL325...

Страница 5: ...or installation A good earth ground is necessary to allow the controller s built in surge and lightning protection circuitry to work effectively All ROTARY GATE SYSTEMS gate operators are supplied wit...

Страница 6: ...ety devices have been included in the layout of the system o A separate pedestrian gate has been included in the gate layout in a location safe from contact with the vehicular gate when it is in the f...

Страница 7: ...7 Access Control Devices The SL 1000 R is compatible with any type of access control device which provides a dry contact relay for activation Installation Figure 2 Gate and Post Layout...

Страница 8: ...8 Figure 3...

Страница 9: ...st 7 Using a 5 16 drill drill a hole into the post through each of the four holes in the mounting plate Tap the holes using a 3 8 16 tap This step may be eliminated if welding the mounting plate to th...

Страница 10: ...ontrol panel Secure the operator motor wire so as to ensure that it will stay c lear of the pinion gear rack gear and gate panel when in motion If necessary the motor wires from the operator can be ad...

Страница 11: ...UT TERMINALS SINGLE INPUT TERMINALS PRIMARY SECONDARY COMM LINK TERMINALS FIRE DEPT INPUT TERMINALS ACCESSORY POWER TERMINALS DISPLAY PROGRAMMING BUTTONS INPUT POWER TERMINALS PLUG IN LOOP DETECTOR CO...

Страница 12: ...OR CURRENT HAS EXCEEDED THE OPEN CURRENT SETTING WHILE OPENING SET MAXIMUM OPEN CURRENT OPEN OBSTR MGT 2 SET OPEN OBSTRUCTION TERMINAL CONNECTED TO COMMON BY BEAM OR SAFETY EDGE OR SIGNAL FROM MGT OBS...

Страница 13: ...HEN STOP AGAIN AT THIS TIME THE AUTO CLOSE TIMER IS DISABLED AND A RENEWED INPUT WILL BE REQUIRED TO START THE GATE AGAIN SHOULD THE GATE BE RESTARTED AND THE OBSTACLE SIGNAL OCCUR AGAIN PRIOR TO REAC...

Страница 14: ...CH PHOTOEYE FOR CLOSE OBSTRUCTION FIRE ACCESS SWITCH SOLENOID LOCK EXTERNAl POWER PHOTOEYE FOR OPEN OBSTRUCTION SINGLE CHANNEL RADIO RECEIVER MAGLOCK GATE EDGE SENSOR FOR REVERSE TWO CHANNEL RADIO REC...

Страница 15: ...T 110 VAC 110 VAC WIRES ARE UNDER TRANSFORMER MOTOR Connect motor wires from SL 1000 R gate operator LIMIT SWITCHES Connect to the wires from the limit switches Black wires go to COMMON RED to OPEN or...

Страница 16: ...f the gate For left hand installations program the controller for left hand operation WHEN CHANGING TO LEFT HAND OPERATION YOU MUST ALSO REVERSE THE MOTOR LEADS IN ADDITION Dual Gate Enable The factor...

Страница 17: ...If the close current load exceeds the programmed maximum load number the operator will stop reverse a short distance then stop again If after restart the overload or a close obstacle happens again be...

Страница 18: ...o ne operator for delayed opening and the other operator for delayed closing The Stagger Delay Time programming function see below sets the length of the delay NOTE This function will only be displaye...

Страница 19: ...is set for Open Immediate alternately the controller can be set for Fail Secure Open Immediate or Close Immediate Fail Safe If the AC power fails and the battery voltage drops below 17 volts 5 second...

Страница 20: ...med to open for 1 to 99 seconds the stop before reaching the open limit When a Mid travel stop position time has been programmed the gate will still fully open if the Fire Department input is triggere...

Страница 21: ...s function will not erase radio transmitters Transmitters must be deleted with the two functions above DO NOT RESET CONTROLLER WITHOUT CONSULTING TECHNICAL SUPPORT AT 877 331 4747 FUNCTION CL ENTER WH...

Страница 22: ...osing at any time Single Input Opens the gate if it s closed and closes th e gate if it s open open close programming option Activating the input while the gate is moving will reverse the gate Can be...

Страница 23: ...run alarm will beep twice as fast and continue for five minutes after the gate stops The sounder will chirp every five seconds when the gate is idle Correct the trouble close case replace battery or...

Страница 24: ...ndicated by EN 04 on the APeX display To clear this error press the RESET button on the out side of the control box and give the system an OPEN or CLOSE signal Model SL 1000 R Maintenance Battery Main...

Страница 25: ...in your area THIS WARRANTY APPLIES ONLY TO THIS PRODUCT WHEN INSTALLED BY A QUALIFIED DEALER AND NOT TO ANY ACCESSORIES THE GATE PANEL ITSELF OR ANY GATE SUPPORT HARDWARE THIS WAR RANTY ONLY COVERS TH...

Отзывы: