20
Advanced Controller Programming (Cont.)
Soft Start/Stop Duration
This function causes the operator to start and stop slowly,
reducing wear and tear (at the full open or closed positions
only). The factory default sets the Soft Start/Stop Duration to 3
seconds. NOTE: AFTER ADJUSTING THIS SETTING, THE
OPEN (OC) AND CLOSE (CC) CURRENT SENSING
SETTINGS WILL HAVE TO BE READJUSTED.
Reset Cycle Count
The controller counts the number of times the operator has
been activated and can display the count rounded off to the
nearest 1000. To reset the cycle count, press and hold the
ENTER
button for 2 seconds while the Cycle Count is
displayed. If the Maintenance Alert has been triggered,
resetting the cycle count will also reset the Maintenance Alert
indicator.
Maintenance Alert Trigger
The controller has a
MAINT ALERT
indicator that can be
programmed to light when the number of activations exceeds a
set number of cycles. The factory default sets the
Maintenance Alert Trigger to 10,000 cycles. The Maintenance
alert Trigger can be programmed for 5, 10, 15, 25 thousand
cycles. The Maintenance Cycle Count can be reset
independently from the operator’s absolute Cycle Count.
Mid-Travel Stop Position
The controller can be programmed so that the gate will stop at
mid-travel point instead of fully opening. This can be useful in
installations where a large gate, that takes a long time to open
and close fully, only needs to be opened partway to allow
traffic to pass.
The factory default sets the controller for full open operation.
Alternately, the controller can be programmed to open for 1 to
99 seconds the stop, before reaching the open limit.
When a Mid-travel stop position time has been programmed,
the gate will
still fully open
if the Fire Department input is
triggered, if the
OPEN
button is held down beyond the Mid -
travel stop position, or a reverse obstacle or loop input is
triggered.
NOT:
The Mid-travel stop feature is disables when dual gate
operation is enabled for paired units.
Motor Type Selection
The motor type selection is set at the factory. If it becomes
necessary to reset the motor type, it should be set to:
-
DC motor with electro nic soft start/stop (d2)
SOFT START DISABLED
SET SOFT START DIRATION
TIME
FROM 1 TO 10 SECONDS
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
FUNCTION
“SS
”
SOFT
START/STOP
DISPLAY SHOWS NUMBER OF OPERATION
CYCLES (OPEN OR CLOSE) ROUNDED TO THE
NEAREST 1000
OPTIONS
FUNCTIION
“CT”
NOTE: PRESS ENTER FOR 2 SECONDS WHILE
THE “CT” FUNCTION IS DISPLAYED TO RESET
CYCLE TIMER TO ZERO
RESET CYCLE
COUNT
DISABLES THE MAINTENANCE ALERT
FUNCTION
SETS THIS MAINTENANCE ALERT TRIGGER
FOR 5, 10, 15, OR 25 THOUSAND CYCLES
RESETS THE MAINTENANCE ALERT
INDICATOR AND SETS THE MAINTENANCE
ALERT COUNT TO ZERO
OPTIONS
FUNCTION
“MA
”
MAINTENANCE
ALERT TRIGGER
OPTIONS
PRESS UP OR DOWN
TO CYCLE THROUGH
OPTIONS
PRESS ENTER TO
SELECT AN OPTION
MID-TRAVEL STOP DISABLED
(GATGE RUNS FULL TRAVEL)
SET LENGTH OF OPENING TIME
FROM 1 TO 99 SECONDS
FUNCTION
MID-TRAVEL
STOP POSITION
“MT”
MOTOR TYPE
SELECTION
AC MOTOR ONLY
DC MOTOR ONLY
DC MOTOR WITH SOFT START/STOP
3 PHASE MOTOR
AC MOTOR PRIMARY WITH DC MOTOR
BACKUP WITH BRAKING
AC MOTOR PRIMARY WITH DC MOTOR
BACKUP WITH SOFT START/STOP
FUNCTION
OPTIONS
“MO”
PRESS UP OR DOWN
TO CYCLE THROUGH
OPTIONS
PRESS ENTER TO
SELECT AN OPTION