18
Advanced Controller Programming
Entering Advanced Programming Mode
To access and program the advanced Programming functions,
for each programming session. Advanced Programming must
be enabled.
After exiting programming, the Advanced Programming
functions will be available on the programming display
during the next programming session unless the operator
has run 50 or more cycles. After that, Advanced
Programming must be enabled again.
Maximum Run Time
The factory default for the maximum Run Time is 99 seconds.
Each time the operator starts, the timer will start counting
down. If an open or close limit is not reached or an obstacle or
reversing input is not received before the timer expires, the
operator will stop, the unit locks out and the alarm sounds. The
timer can be set for 10 to 99 seconds.
Single Button Input Setup
This function is used to set up the operator for single button
controls and radio receivers.
The factory default sets the
SINGLE
input terminal so
successive inputs will cycle the operator in OPEN -STOP-
CLOSE-STOP order.
Alternatively, the
SINGLE
input can be set to cause the gate to
OPEN unless the gate is fully open. If the gate is fully open, the
input will cause the gate to C LOSE.
Stagger Mode
This function is used in dual gate installations only.
The
factory default sets the Stagger Mode to OFF. In dual gate
installations the two operators communicate through the 3 -wire
COMM LINK
interface. When using the Stagger Mode, set o ne
operator for delayed opening and the other operator for
delayed closing. The Stagger Delay Time programming
function (see below) sets the length of the delay.
NOTE:
This function will only be displayed if dual gate
operation is selected.
This function is used in dual gate installations only.
The
factory default sets the Stagger Time to 0 seconds (OFF). The
Stagger Time sets the delay for the Stagger Mode. The
Stagger time can be set from 1 -99 seconds.
NOTE:
This function will only be displayed if dual gate
operation is selected.
FUNCTION
“AD”
ADVANCED PROGRAMMING FUNCTIONS
WILL NOT BE DISPLAYED
ADVANCED PROGRAMMING OPTIONS
WILL BE DISPLAYED
PRESS UP OR DOWN
TO CYCLE THROUGH
OPTIONS
PRESS ENTER TO
SELECT AN OPTION
NOTE: ADVANCED PROGRAMMING
WILL STAY ENABLED AFTER EXITING
PROGRAMMING UNTIL THE GATE
CYCLES 50 TIMES.
ADVANCED
PROGRAMMING
FUNCTION
“RT”
DISPLAY SHOWS CURRENT
MAXIMUM RUN TIME SETTING
PRESS ENTER
WHILE DISPLAY IS FLASHING, PRESS
UP OR DOWN TO CHANGE THE
MAXIMUM RUN TIME (10 -99 SECONDS)
PRESS ENTER TO STORE THE VALUE
OPTIONS
ENTER
ENTER
MAXIMUM RUN
TIMER
FUNCTION
SINGLE BUTTON
INPUT SETUP
“SB”
SINGLE INPUT WILL CYCLE OPERATOR
IN ORDER OF OPEN-STOP-CLOSE-STOP
SINGLE INPUT WILL OPEN OPERATOR,
IF OPERATOR IS ALREADY OPEN, SINGLE
INPUT WILL CLOSE OPERATOR
DISABLES STAGGER FUNCTION
SETS THIS OPERATOR FOR DELAYED OPEN
SETS THIS OPERATOR FOR DELAYED CLOSE
FUNCTION
“SM”
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
STAGGER
MODE
DUAL GATES
ONLY
STAGGER TIMER DISABLED
SET STAGGER DELAY VALUE
1 TO 99 SECONDS
“ST”
FUNCTION
STAGGER
DELAY TIME
OPTIONS
RESS UP OR DOWN TO
CYCLE THROUGH
OPTIONS
PRESS ENTER TO SELECT
AN OPTION