2-Wire Photoelectric Smoke Detector 

Installation Manual

 

1.

 

Introduction 

The SA-64-2W is a 2-wire conventional smoke detector for fire control 

panel of type Notifier SFP2404. 
The smoke sensor unit can easily be plugged into or detached from the 

wired base unit (AS-64B-2W) for cleaning and maintenance purposes. 
The sensor chamber is engineered to sense smoke by a wide range of 

combustion sources. The chamber is well protected and proofed from 

insects and dust contamination. A LED indicator on the sensor unit 
shows the operating status and Alarm mode. 
The SA-64-2W smoke detector has a low profile and a professional and 
trendy appearance. 

Figure 1: SA-64-2W 

 

2.

 

Technical Specifications 

2.1

 

Electrical Characteristics 

System Voltage (Nominal) 

24 VDC 

Min. Operating Voltage 

8.5 VDC 

Max. Operating Voltage 

30 VDC 

Avg. Standby Current 

30 µA 

Sensitivity 

EN: xx dB/m 
UL: 0.5~4% /ft (2.5% /ft normal) 

Alarm 

Type: current, latch 
Rate: 35 mA 

Remote Annunciation 

Type: N.O. 
Rate (during alarm): 12/24 V, 35/70 mA max 

2.2

 

Environmental Characteristics 

Environment 

Indoor 

Operating Temperature Range 

0°C to 37.8°C (32°F to 100°F) 

Storage Temperature Range 

-20°C to 70°C (-4°F to 158°F) 

Operating Humidity Range 

0 to 95% RH (non-condensing) 

2.3

 

Physical Characteristics 

Weight 

120 g (4.23 oz) 

Dimensions (L x W x H) 

121.9 x 121.9 x 34 mm (4.8 x 4.8 x 1.34 in.) 

Compliance with Standards 

EN54-7: 2001 +A1+A2, UL268 
EC certificate number: 0843-CPD-XXXX 

2.4

 

Modes of Operation 

Operation Mode 

Red LED flash indication every 10 seconds 

Alarm Mode 

The detector sends an alarm signal to the Fire 
Control Panel. The LED remains on. 

Trouble Mode 

Trouble is detected by Fire Control Panel (if the EOL 

resistor is removed) 

2.5

 

Signaling and Events 

Tamper Event 

When the sensor is disconnected from the base or 

the base unit from the ceiling. 

Signaling Type 

Red LED on detector 

Report Types 

Alarm, Tamper, Remote Annunciation 
Alarm Report: 

 

Alarm Report – The detector announces an 
alarm via the alarm annunciation terminal. The 
event ends only by cutting power from the 
panel momentarily. 

 

Tamper Report – If detector is removed or line 
was cut. Use EOL (depending on panel request) 
according to Figure 4 in Section 

 

3.5. 

 

Remote Annunciation Report – GND on output 
during event. The event ends only by cutting 
power from the panel momentarily. 

3.

 

Installation 

3.1

 

Choosing a Mounting Location 

A smoke detector should be installed according to NFPA (National Fire 

Protection Association) Standard 72. For complete coverage in 
residential units, smoke detectors should be installed in all rooms, halls, 

storage areas, and basements. At the least, one detector should be 

placed on each floor and in each sleeping area. 
Install smoke detectors as close to the center of the ceiling as possible 

or at least 10 cm (4 inches) away from any wall or corner. 
Do NOT locate smoke detectors at the top of peaked or gabled 

ceilings; the dead air space in these locations may prevent the unit 

from detecting smoke. Avoid areas with turbulent air flow such as near 
doors, fans or windows. Rapid air movement around the detector may 

prevent smoke from entering the unit and affected the accuracy. 

3.2

 

Smoke Detector Limitations 

 

Smoke detectors will not sense a fire if the smoke does not reach 

the sensor. 

 

Some smoke detectors cannot easily be seen from every location. 

Connect a remote announcement light that can be seen more 

easily from other parts of the house. 

 

Smoke from a slow fire rises slowly and may not reach the smoke 

detector until the fire gets bigger. 

 

To keep your smoke detectors working properly, be sure to 

maintain the unit according manufacturer’s recommendations and 

UL and NFPA standards 