Rosslare AS-34 Скачать руководство пользователя страница 1

 

AS

-

34/SA-34G/H/W

 

Installation Instructions 

Optical Smoke Detector 

 

0706-00 

 

1.

 

Introduction 

The AS-34 optical smoke detector is a standalone supervised smoke 

detection and warning system for use in family homes or other 

residential locations. The unit is easy to install and powered by a single 

9V battery, which can sustain the unit’s operation for up to 1 year. The 

smoke detector registers smoke particles by their photoelectric effect, 

making it especially sensitive to smoky and smoldering fires that burn 

slowly for many hours before bursting into flames. For example, this type 

of fire might be caused by a cigarette burning against a sofa. The 

detector can connect to Rosslare's security system panel, or to any 

standard wireless security system. To connect the AS-34 smoke detector 

to a wired or wireless system, mount it on Rosslare's SA-13G (wireless; 

433.92MHz), SA-13H (wireless, 868.35MHz), or SA-13W (wired) base.  

NOTE:

When the unit's battery is running low, the unit beeps, flashes its LED 

indicator, and sends an alert message to its host control panel. 

 A fully mounted unit (AS-34 + SA-13G/H/W) is referred to as SA-

34G/H (wireless) or SA-34W (wired). 

NOTE: 

The AS-34 Smoke Detector is not designed to serve as a substitute 

for a primary fire detection system. 

 

Figure 1. AS-34 Optical Smoke Detector 

2.

 

Technical Specifications 

2.1

 

Electrical Characteristics 

AS-34 Detector Current: 

Standby

 

 

 

Alarm: 15–25 mA 

: 10 µA 

SA-13G/H Base Current: 

Standby: 16 µA 

 

 

 

Transmitting distance: up to 200m 

 

 

 

 

in open space 

 

 

 

Transmitting: 16 mA 

SA-13W Base Current: 

NC output: 

 

 

 

Standby: 21 mA 

 

 

 

 

Operating: 7 mA 

 

 

NO output: 

 

 

 

Standby: 10 mA 

 

 

 

 

Operating: 23 mA 

Battery (for SA-34G/H): 

IEC 6LF22 or MN1604 (9V Alkaline) 

Battery Life: 

 

 

1 year 

Low Battery Detection: 

2.2

 

Environmental Characteristics 

Last 7 days of battery life 

Use Environment 

 

Indoor  

Operating Temperature: 

0°–40°C (32°–104°F) 

Operating Humidity: 

2.3

 

Physical Characteristics 

10% to 90% Non-Condensing 

Sensitivity: 

 

 

0.5% ± 4% FT nominal 

Indicators: 

 

 

LED and siren 

Siren Volume:   

85 dB at 3m 

Dimensions:
 

 

 

4.66 x 4.21 x 1.57 inch 

 

 

SA-34G/H:  126.5 x 124 x 63.7 mm 

 

 

 

   (4.98 x 4.88 x 2.5 inch) 

 

 

SA-34W:  121 x 112.6 x 58.5 mm 

 

   

 

AS-34: 118.4 x 107 x 40 mm  

 

 

   (4.76 x 4.43 x 2.3 inch) 

Weight:
 

 

 

SA-34G/H:  307g (10.38 oz) 

 

 

 

AS-34: 130g (4.59oz) 

 

 

 

SA-34W:  192.4g (6.5 oz) 

3.

 

Installation 

The AS-34 is a photoelectric detector, it can be operated as a 

standalone unit or as an alarm system together with the SA-13 wireless 

or wired base. Mount the smoke detector on the ceiling in a central 

area with plenty of air circulation, as described below. 

3.1

 

Location 

For full protection, every room should have a smoke detector fitted. In a 

home with more than one storey, at least one smoke detector should 

be fitted on each landing and at the bottom of the staircase. Ensure 

the alert siren is audible from every room. 

Do not fit the smoke detector: 

 

In areas where the temperature falls below 0°C or reaches above 

40°

 

In humid areas, such as bathrooms, kitchens, or shower rooms 

 

In a garage or other areas where exhaust gases may cause false 

alarms 

 

Close to radiators or ventilation vents, which disrupt the airflow 

 

In a workshop or other dusty environment 

3.2

 

Wiring the SA-34W  

For wiring instillations follow the instructions below. 

To set and wire the SA-34W: 

1.  set the alarm output setting to either Normally Open or Normally 

Closed using the select switch on the SA-13W. 

2.  Connect the power between the Security Alarm system and the SA-

13W’s Vin and ground terminal blocks. 

3.  Connect the Tamper outputs to the Security Alarm system’s inputs 
4.  Connect the Alarm terminal blocks to the Security Alarm system, 

refer to the installation manual of the alarm system you are 

connecting the detector to.  

 

Figure 2 Wiring Diagram 

3.3

 

Mounting the Detector 

Before mounting the Detector, ensure that your chosen mounting area 

is not in front of any electrical wiring or pipe work. 

1.  Mark two mounting points in the ceiling according to the base (SA-

13G/H/W) size and holes. 

2.  Drill into the marked points and insert wall plugs. 
3.  Using screws, mount the base onto the ceiling.  
4.  Mount the AS-34 unit on the base (see Figure 3). 

NOTE:

 

 Be careful not to over-tighten the screws. 

Figure 3. Mounting AS-34 on the Base Unit 

AS-34 Standalone 

SA-34G/H Wireless Base  SA-34W Wired Base 

Отзывы: