9–14 • Calibration and Diagnostics
Synergy 1 and Synergy 100 Maintenance Guide (v16-S1)
3. Test the floppy disk drive or USB port as follows:
•
Insert a blank disk or a pre-formatted disk into the drive. If you have a USB port,
insert a blank USB key.
•
Press
Test
to begin the disk read/write test.
•
The menu indicates
Pass
or
Fail
.
This completes the procedure to test the floppy disk drive or USB port of the Synergy 1 switcher.
Panel TX/RX Test
The
Panel TX/RX Test Menu
allows you to test communications with various remote control and
communications ports. A proper loop-back connector is required to conduct the external test.
Use the following procedure to test the TX/RX functions of the Synergy 1 control panel:
1. Navigate to the
Panel Diagnostics Menu 2-2
as follows:
•
Press
HOME
(to display the
Main Menu 1-2
)
•
MORE
(to display
Main Menu 2-2
)
•
Setup
(to display the
Setup Menu
)
•
Panel Diagnostics
(to display
Panel Diagnostics Menu 1-2
)
•
MORE
(to display
Panel Diagnostics Menu 2-2
)
2. Press
TX/RX Test
to display the
Panel TX/RX Test Menu
.
Panel TX/RX Test Menu
3. Test a port as follows:
•
Use the middle
Com Port
knob to select the port you wish to test.
•
If available, attach an appropriate loop-back connector to the port.
•
If a loop-back connector is not available, the system will only be able to perform a
partial test (the UART will be tested, however, the line drivers and receivers will
not). Note that a proper loop-back connector is required to conduct the external test.
•
Press
Test
to begin the TX/RX test.
•
The menu indicates
Pass
or
Fail
for internal and external tests:
~
The internal test checks the UART that generates the serial data stream.
~
The external test also tests the line drivers and receivers.
This completes the procedure to test the TX/RX functions of the Synergy 1 control pane. Repeat the
procedure to test any additional ports.
Note
Peripheral equipment should be disconnected from the selected port
while running the test.
Содержание Synergy 1
Страница 1: ...Ross Video Limited Synergy 1 and Synergy 100 Maintenance Guide Software Version 16 S1...
Страница 10: ......
Страница 16: ...vi Contents Synergy 1 and Synergy 100 Maintenance Guide v16 S1...
Страница 24: ...1 8 Introduction Synergy 1 and Synergy 100 Maintenance Guide v16 S1...
Страница 70: ...3 24 Software Upgrades Synergy 1 and Synergy 100 Maintenance Guide v16 S1...
Страница 108: ...5 12 Frame Processor CPU Board Synergy 1 and Synergy 100 Maintenance Guide v16 S1...
Страница 122: ...6 14 Working with Installed Options Synergy 1 and Synergy 100 Maintenance Guide v16 S1...
Страница 142: ...8 14 Power Supplies Synergy 1 and Synergy 100 Maintenance Guide v16 S1...
Страница 172: ...9 30 Calibration and Diagnostics Synergy 1 and Synergy 100 Maintenance Guide v16 S1...
Страница 186: ...10 14 Control Panel Boards Synergy 1 and Synergy 100 Maintenance Guide v16...
Страница 230: ...13 20 Miscellaneous Options Synergy 1 and Synergy 100 Maintenance Guide v16 S1...
Страница 240: ...IX 10 Index Synergy 1 and Synergy 100 Maintenance Guide v16 S1...