ROSEMOUNT FLANGED SENSOR SPECIFICATIONS
FLANGED SENSOR
FUNCTIONAL
SPECIFICATIONS
Service
Conductive liquids and slurries
Line Sizes
1
/
2
–36 in. (15–900 mm) for Rosemount 8705
3–36 in. (80–600 mm) for Rosemount 8707
Interchangeability
Rosemount 8705 Sensors are interchangeable with 8732 and 8712E
Transmitters. Rosemount 8707 High-Signal Sensors are interchangeable with
8732, 8712E, and 8712H High-Signal Transmitters. System accuracy is
maintained regardless of line size or optional features. Each sensor
nameplate has a sixteen-digit calibration number that can be entered into a
transmitter through the Local Operator Interface (LOI) or the Field
Communicator. In a F
OUNDATION
fieldbus environment, the 8732E can be
configured using the DeltaV
™
fieldbus configuration tool or another
F
OUNDATION
fieldbus configuration device. No further calibration is necessary.
Upper Range Limit
39 ft./s (12 m/s)
Process Temperature Limits
PTFE Lining
–20 to 350 °F (–29 to 177 °C)
ETFE Lining
–20 to 300 °F (–29 to 149 °C)
PFA Lining
-20 to 350 °F (-29 to 177 °C)
Polyurethane Lining
0 to 140 °F (–18 to 60 °C)
Neoprene Lining
0 to 176 °F (–18 to 80 °C)
Linatex Lining
0 to 158 °F (–18 to 70 °C)
Ambient Temperature Limits
–30 to 150 °F (–34 to 65 °C)