IB-106-340
5-13
DIAGNOSTIC
ALARMS
TEST
POINTS
HEATER T/C
HEATER
O2 CELL
CALIBRATION
CALIBRATION RECOMMENDED
O2 CELL mV +
O2 CELL mv -
HEATER T/C +
HEATER T/C -
INC
INC
DEC
DEC
HIGH
GAS
LOW
GAS
CAL
TEST GAS +
PROCESS -
% O2
SW2
TP1
J1
TP2
TP3
RED
YEL
GRN
ORG
TP4
TP5
TP6
ON
22220043
Figure 5-11. Fault 11, EEPROM Corrupt
k.
Fault 11, EEPROM Corrupt. The O2 CELL
LED flashes four times, pauses for three seconds,
and repeats (Figure 5-11).
1. This alarm can occur if the EEPROM is
changed for a later version. At power up,
the EEPROM is not updated.
2. To correct this problem, power down and
then restore power. The alarm should clear.
3. If the alarm occurs while the unit is running,
there is a hardware problem on the micro-
processor board.
4. If cycling the power does not clear the
alarm, see paragraph 6-5b, Electronic As-
sembly Replacement.
Содержание Oxymitter 4000
Страница 19: ...IB 106 340 xv ...