Reference Manual
00809-0100-4664, Rev BA
January 2010
Rosemount 8712
2-6
Figure 2-2. Rosemount 8712
Electronics Board and Hardware
Switches
Conduit Ports
and Connections
Both the sensor and transmitter junction boxes have ports for
1
/
2
-in. NPT
conduit connections. These connections should be made in accordance with
local or plant electrical codes. Unused ports should be sealed with metal
plugs. Proper electrical installation is necessary to prevent errors due to
electrical noise and interference. Separate conduits are not necessary for the
two cables, but a dedicated conduit line between each transmitter and sensor
is required. Shielded cable must be used for best results in electrically
noisy environments.
Example 1:
Installing flanged sensors into an IP68 area. Sensors must be
installed with IP68 cable glands and cable to maintain IP68 rating. Unused
conduit connections must be properly sealed to prevent water ingress. For
added protection, dielectric gel can be used to pot the sensor terminal block.
Example 2:
Installing flowmeters into explosion proof/flameproof areas.
Conduit connections and conduit must be rated for use in the hazardous area
to maintain flowmeter approval rating.
Conduit Cables
Run the appropriate size cable through the conduit connections in your
magnetic flowmeter system. Run the power cable from the power source to
the transmitter. Run the coil drive and electrode cables between the flowmeter
and transmitter. Refer to Electrical Considerations for wire type. Prepare the
ends of the coil drive and electrode cables as shown in Figure 2-3. Limit the
unshielded wire length to 1-inch on both the electrode and coil drive cables.
Excessive lead length or failure to connect cable shields can create electrical
noise resulting in unstable meter readings.
•
Installed signal wiring should not be run together and should not be in
the same cable tray as AC or DC power wiring.
•
Device must be properly grounded or earthed according to local
electric codes.
•
Rosemount combination cable model number 08712-0752-0001 (ft) or
08712-0752-0003 (m) is required to be used to meet EMC
requirements.
Содержание 8712
Страница 2: ......
Страница 4: ......
Страница 26: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 2 16 ...
Страница 84: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 4 46 ...
Страница 102: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 5 18 ...
Страница 114: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 6 12 ...
Страница 131: ...Reference Manual 00809 0100 4664 Rev BA January 2010 B 7 Rosemount 8712 Figure B 1 CSA Installation ...
Страница 132: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 B 8 Figure B 2 Factory Mutual Hazardous Locations ...
Страница 154: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 D 6 ...
Страница 194: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 E 40 ...
Страница 208: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 F 14 ...
Страница 211: ......