Reference Manual
00809-0100-4530, Rev DD
May 2016
4.8
F
OUNDATION
™
Fieldbus
4.8.1
Power requirements
Terminals in the transmitter housing provide connections for signal cables. The Rosemount
5300 Transmitter is powered over F
OUNDATION
Fieldbus with standard fieldbus power
supplies. The transmitter operates with the following power supplies:
Grounding - F
OUNDATION
Fieldbus
Signal wiring of the fieldbus segment cannot be grounded. Grounding out one of the signal
wires will shut down the entire fieldbus segment.
Shield wire ground
To protect the fieldbus segment from noise, grounding techniques for shield wire usually
require a single grounding point for shield wire to avoid creating a ground loop. The ground
point is typically at the power supply.
Approval type
Power supply (Vdc)
None
9 - 32
Non-sparking/Energy limited
9 - 32
Intrinsically Safe
9 - 30
FISCO
9 - 17.5
Explosion-proof/flameproof
16 - 32
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...