3.2.8
Recommended mounting position for liquids
Tank conditions are recommended to be carefully considered when finding the appropriate
mounting position for the transmitter. The transmitter should be mounted so the influence
of disturbing objects is reduced to a minimum.
In case of turbulence, the probe may need to be anchored to the bottom. See
for more information.
Figure 3-14. Mounting Position
A. Inlet pipe
B. Agitator
C. Heating coils
When mounting the transmitter the following guidelines should be considered:
Do not mount close to inlet pipes.
Do not mount close to agitators. If the probe can move to within 12 in. (30 cm)
away from an agitator, a probe tie-down is recommended.
If the probe tends to sway from the turbulent conditions in the tank, the probe
should be anchored to the tank bottom.
Avoid mounting near heating coils.
The probe should not come into contact with the nozzle or other objects in the
tank.
Position the probe so it is subject to a minimum of lateral force.
Note
Violent fluid movements can cause forces that could break rigid probes.
A
C
B
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...