Rosemount 5300 Series with HART® to Modbus® Converter
May 2016
Reference Manual
00809-0100-4530, Rev DD
387
Rosemount 5300 Series with HART® to Modbus® Converter
J.8.1
Using RRM to change communication parameters
Note
To change Modbus communication parameters, the Rosemount 5300 Series Transmitter
must use HART address 1, the default address.
Note
After changing communication parameters, disconnect the HART modem and wait at least
60 seconds for the change to take effect.
In case the MA/MB terminals are used for connection to the HMC, disconnect the RS-485
Converter, cycle power to the transmitter and wait up to 60 seconds for the change to take
effect.
To change the Modbus address and communication parameters in Rosemount Radar
Master (RRM):
1.
Start RRM and connect to the transmitter.
2.
In RRM, select
Setup
>
General
.
3.
Select the
Communication
tab.
4.
Click the
Modbus Setup
button.
Modbus Setup
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...