6.
Connect the transmitter head on the housing support, making sure the M50 nut is
properly tightened.
D.4
Remote housing configuration
When using remote housing, the remote connection length should be configured. If the
Remote Housing is ordered with a transmitter, it is configured in the factory.
In Rosemount Radar Master, select
Setup
>
Tank
.
Under the
Probe
tab, Remote Housing length can be selected. Click the
Store
button to save
changes.
In the Field Communicator, Remote Housing can be set with HART
®
command [2, 3, 1, 4, 2].
Note
When disconnecting a remote housing cable from a probe in low temperatures, -22 °F (-30
°C), Radar Master may not show that the probe is missing.