Reference Manual
00809-0100-4530, Rev DD
320
C.8.3
Calibrate Dynamic Vapor Compensation function
Check if calibration is needed on-site
Note
When installing a device with Dynamic Vapor Compensation, do not upload a backup file
from another device.
Type
Action
Probe type 3V (coaxial) without
remote housing
The Dynamic Vapor Compensation function of this
Rosemount 5300 Series Transmitter has been calibrated at
factory.
Calibration is only needed if:
The transmitter is reset to factory settings. Reset
removes pre-calibration of the Dynamic Vapor
Compensation function.
A spare or replacement Rosemount 5300
Transmitter head is mounted on the supplied
Dynamic Vapor Compensation probe.
Probe type 3V (coaxial) with remote
housing
Calibration is always needed on-site during the commission
phase.
Probe type 4U (rigid single)