Reference Manual
00809-0100-4530, Rev DD
May 2016
To calibrate the analog output current:
1.
Start RRM and make sure that the transmitter communicates with the PC (see
).
2.
In the
Device Config/Setup
toolbar, select the
Output
icon.
3.
Select the
Analog Out 1
tab.
4.
Select the
Calibrate DAC
button.
5.
Follow the instructions to calibrate the 4 mA and the 20 mA outputs.
7.9
Level and distance calibration
Level and distance calibration may be necessary when using a nozzle or pipe or if there are
disturbances in the near zone caused by a physical object.
Non-metallic (e.g. plastic) vessels and installation geometry may introduce an offset for the
zero reference point. This offset may be up to ± 25 mm. The offset can be compensated for
using Distance Calibration.
When calibrating the transmitter, it is important that the product surface is calm and that
the tank is not being filled or emptied.
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...