Reference Manual
00809-0100-4530, Rev DD
May 2016
5.11
Tri-Loop
™
HART-to-Analog converter
The Rosemount 333 HART Tri-Loop HART-to-Analog signal converter is capable of
converting a digital HART Burst signal into three additional 4-20 mA analog signals.
To set the Rosemount 5300 Series Transmitter up for the HART Tri-Loop:
1.
Make sure the Rosemount 5300 Series Transmitter is properly configured.
2.
Assign transmitter variables Primary Variable, Secondary Variable etc.
HART command [2,1,1].
RRM:
Setup
>
Output/General
3.
Configure variable units: length, level rate, volume and temperature.
HART command [2,2,2,5].
RRM:
Setup
>
General/Units
4.
Set the Rosemount 5300 Series in Burst Mode.
HART command [2,2,4,2].
RRM:
Setup
>
General/Communication
Note
Using a HART revision 7 device, the Rosemount 5300 Series supports up to 3 Burst
messages. It can burst Cmd 1, 2, 3, 9, 33, 48. For command aggregation, Cmd78 is used.
Supported burst trigger modes in HART 7: Continuous, Windowed, Falling, and Rising.
Variables
assignment
Variable
units
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...