128
Reference Manual
00809-0100-4530, Rev DD
May 2016
temperature). The relationship between the transmitter measurement and the calculated
measurement will be linear.
Indirect square root
Select indirect square root when the desired output is an inferred measurement based on
the transmitter measurement and the relationship between the sensor measurement and
the inferred measurement is square root (e.g. level).
XD_SCALE and OUT_SCALE
The XD_SCALE and OUT_SCALE each include three parameters: 0%, 100%, and engineering
units. Set these based on the L_TYPE:
L_TYPE is direct
When the desired output is the measured variable, set the XD_SCALE to represent the
operating range of the process. Set OUT_SCALE to match XD_SCALE.
L_TYPE is indirect
When an inferred measurement is made based on the sensor measurement, set the
XD_SCALE to represent the operating range that the sensor will see in the process.
Determine the inferred measurement values that correspond to the XD_SCALE 0 and 100%
points and set these for the OUT_SCALE.
L_TYPE is indirect square root
When an inferred measurement is made based on the transmitter measurement and the
relationship between the inferred measurement and sensor measurement is square root,
set the XD_SCALE to represent the operating range that the sensor will see in the process.
Determine the inferred measurement values that correspond to the XD_SCALE 0 and 100%
points and set these for the OUT_SCALE.
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...