Section 3. MST/WLS Installation
3.3.3
Custody Transfer
Applications
For Custody Transfer applications, API chapter 7 recommends a minimum of
one temperature element per 3 meters (10 feet) as illustrated in Figure 3-3.
Emerson Process Management/Rosemount Tank Gauging
may in some
cases recommend even more temperature elements for Custody Transfer
tanks, depending on how the tanks are operated.
Figure 3-3. Recommended
temperature element positions
for Custody Transfer
applications
Table 3-1. Number of spot
sensors for various tube lengths
Example
5 spot sensors and H=12 m.
A=12/(5-1)=3 m.
The position of a temperature element is measured from the Tank Zero Level.
See the
Rosemount Raptor System Configuration Manual (Document no.
300510EN)
for more information about how to use the TankMaster WinSetup
software to configure temperature elements for average temperature
calculations.
0.5-1 m
(1.6-3.2 ft)
0.5-1 m
(1.6-3.2 ft)
Minimum level
Tank Zero level
Tube length
Number of temp. elements
< 9 m
4
9 - 15 m
5
> 15 m
6