Section 4. 2240S Installation
4.4.7
Typical
Installations
The example below (Figure 4-3) illustrates a Raptor system with terminators
at both ends of the fieldbus segment as required in a F
OUNDATION
fieldbus
system. In this case terminators are enabled in the Rosemount 2410 Tank
Hub and a Raptor field device at the end of the network segment.
Figure 4-3. Example of a Raptor
Tankbus connection for a single
tank
The maximum distance between the 2410 Tank Hub and the field devices on
the tank depends on the number of devices connected to the Tankbus and the
quality of cables.
See chapter “Electrical Installation” in the
Rosemount 2410 Reference
Manual
(Document no. 305030en) for more information about cable selection,
power budget, and the Raptor Tankbus.
See chapter “Typical installations” in the
Rosemount 2410 Reference Manual
(Document no. 305030en) for more examples of how to install a Raptor
system.
5900S Radar
Level Gauge
2240S Multi-input
Temperature Transmitter
Built-in terminator
Tankbus
Built-in
terminator
enabled on the
last device
2230 Display
2410 Tank Hub with
intrinsically safe power
supply, integrated power
conditioner, and built-in
terminator
Tankbus length up to 1000 meter depending
on number of devices and cable quality
Содержание 2240S
Страница 2: ......
Страница 4: ......
Страница 58: ...Reference Manual 300550EN Rev AA December 2010 Rosemount 2240S 5 16 Section 5 Configuration Operation ...
Страница 84: ...Reference Manual 300550EN Rev AA December 2010 Rosemount 2240S A 6 Appendix A Reference Data ...
Страница 96: ...Reference Manual 300550EN Rev AA December 2010 Rosemount 2240S B 12 Appendix B Product Certifications ...
Страница 99: ......