Reference Manual
300550EN, Rev AA
December 2010
3-7
Rosemount 2240S
Section 3. MST/WLS Installation
3.4 WATER LEVEL
SENSOR
The water level sensor probe, with integrated temperature elements, is
attached at the lower end of the flexible protection tube. A weight is attached
to stabilize the tube as illustrated in Figure 3-4:
Figure 3-4. Water Level Sensor
with integrated temperature
sensors
As an option, the tube may be stabilized by putting a concentric weight above
the WLS probe, instead of at the end, in order to ensure that measurements
are performed as close to the tank bottom as possible. Also, the eyebolt at the
end of the tube can be removed.
Upper Sensor Limit (100%)
Lower Sensor Limit (0%)
WLS Probe Active Length
Standard: 500 mm (19.7 in.)
Option: 1000 mm (39.4 in.)
Recommended distance:
0.5 to 1.5 m (1.6 to 4.9 ft)
Weight
350 m
m
(13.8 i
n
.)
Nuts to adjust the
sensor position