![Rosemount 1199 Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/rosemount/1199/1199_reference-manual_1487371050.webp)
Reference Manual
00809-0100-4002, Rev BB
November 2012
Rosemount 1199
4-12
If the device has a display and you want to configure it to something other
than standard default, which is Engineering units & %, go to step 7.
Scale Display
7.
After the transmitter is installed you can scale the display to match the
DCS or PLC as required. As an example, in Figure 4-8 on page 4-10
if the required display should be 0 to 81 inH
2
O, this can be done
using a HART field communicator. See the following steps for the
3051S or the 3051C. Often 0 to 100% is sufficient.
NOTE
Depending on the HART device (Hand held/ AMS) DD the following steps
may be slightly different.
NOTE
In both cases with the transmitter ranged -112.08 to -31.08 inH
2
O, the display
will show 0 inH
2
O at (4 mA) and 81.00 inH
2
O at (20 mA).
For the
Rosemount 3051S
, in the HART
menu tree, go to the Scaled variable
Config (under guided set up). Follow the
steps below. Bold text indicates entered
value.
For the
Rosemount 3051C
, in the
HART communicator, go to
Configure
Display
and follow the following steps:
1.
Enter SV unit:
(enter)
inH
2
O
2.
Select Scaled data option:
(select)
Linear
3.
Enter Pressure value position 1:
(enter)
-112.08
4.
Enter Scaled Variable position 1:
(enter)
0
5.
Enter Pressure value position 2:
(enter)
-31.08
6.
Enter Scaled Variable position 2
(enter)
81
7.
Enter Linear Offset:
(enter)
0.00
3051S go to Display (under manual
setup)
1.
Display Option
(Select)
Custom
meter Display
2.
Decimal Places
(Enter)
3
(Send
before step 3)
3.
Upper Range Value
(enter)
81.000
4.
Lower Range Value
(enter)
0.000
5.
Transfer Function
(select)
Linear
6.
Units
(Enter)
inH
2
O
1 Pressure
OFF
2
Scaled Variable
ON
3 Module Temperature
OFF
4 Percent of Range
OFF
Содержание 1199
Страница 2: ...This page intentionally left blank ...
Страница 4: ...This page intentionally left blank ...
Страница 8: ...Reference Manual 00809 0100 4002 Rev BB November 2012 Rosemount 1199 TOC 4 ...
Страница 20: ...Reference Manual 00809 0100 4002 Rev BB November 2012 Rosemount 1199 2 10 ...
Страница 38: ...Reference Manual 00809 0100 4002 Rev BB November 2012 Rosemount 1199 3 18 ...
Страница 60: ...Reference Manual 00809 0100 4002 Rev BB November 2012 Rosemount 1199 5 10 ...
Страница 81: ...This page intentionally left blank ...