Technical data
Version 1
RES-5009
Page 91
Careless and uncontrolled disposal can cause damage to the environment and human health. Help protect
the environment and human health, and dispose of the product or recycle it responsibly.
15
Technical data
CAUTION
Operation of the temperature controller outside of these technical specifications results in loss of
warranty and can cause defects.
NOTE
This device must not be disposed of in the residual waste bin!
Design
Housing for electrical cabinet mounting
Can be snapped on to TS35 top hat rail (35mm) in accordance with EN 60715
Basic surface: 90x75 mm; depth: 135 mm (incl. connection terminals)
Line voltage
Connected between neutral conductor and an outside conductor:
110 VAC -15%…300 VAC +10%
or
Connected between two outside conductors:
110 VAC -15%…480 VAC +10%
CAUTION
The voltage between outside conductor and earth must not exceed
300VAC.
Power supply
Symmetrical TN or TT network
Overvoltage category III
CAUTION
Operation in voltage-free network (e. g. IT network) only after checking
with ROPEX.
Line frequency
47…63 Hz, automatic frequency adjustment in this range
Current consumption
(Primary current of the
impulse transformer)
I
max
= 5 A (ED = 100%)
I
max
= 25 A (ED = 20%, playing time 1 min. A booster must be used for higher
power requirements.)
24VDC power supply
Terminals 5+7
24 VDC, I
max
= 100 mA
Tolerance: ±10%
SELV or PELV supplied from maximum 300VAC, Cat II
Measurement range
Secondary voltage U
R
: 0.4 ...120 VAC (lower voltages with MOD 01, higher volt-
ages with a ROPEX series resistor)
Secondary current I
R
: 30…500 A with current transformer PEX-W4/W5 (lower
currents: Secondary cables lead through the current transformer several times,
higher currents with a load resistor)
The dimensioning is made in the ROPEX application report.