CANopen
Page 60
RES-5009
Version 1
The blinking codes of the green run LED have the following meaning:
10.6
Heartbeat
10.6.1 Producer heartbeat
The RESISTRON
®
Temperature Controller RES-5009 does not generate heartbeat messages by default. With the
help of CANopen object 1017
h
, the producer heartbeat can be set project-specifically.
CAUTION
The use of the producer heartbeat is strongly recommended. The producer heartbeat should be
monitored in the CANopen master. With this mechanism, an interruption in communication with
the RESISTRON
®
Temperature Controller RES-5009 can be quickly detected by the CANopen
master.
When a new heartbeat time is set using object 1017
h
, the corresponding counter is restarted. The next heartbeat
message is sent after the configured time after setting the object. Therefore, a longer time interval between two
heartbeat messages can occur once in the heartbeat configuration.
10.6.2 Consumer heartbeat
The RESISTRON
®
Temperature Controller RES-5009 can monitor heartbeats of up to 4 CANopen nodes. The
configuration is carried out via CANopen object 1016
h
, sub index 1 to 4. By default, heartbeat monitoring is not
active. If a heartbeat error is detected, a currently active welding process is interrupted and the device is put into
the PreOperational state. In addition, an emergency message is sent.
CAUTION
It is strongly recommended to configure the monitoring of the consumer heartbeats project-spe-
cifically in the RESISTRON
®
Temperature Controller RES-5009. In case of CANopen communica-
tion problems, an uncontrolled welding process can thus be avoided.
Double flash
Error event
A heartbeat error has been detected (heartbeat consumer).
On
Bus off
The CAN controller is in the bus off state.
Run LED (RUN)
State
Description
Flickering
(10 Hz)
AutoBaud / LSS
automatic baud rate detection “AutoBaud” or Layer Setting
Services “LSS” is active
(Alternate flickering with the error LED)
Blinking (2.5 Hz)
Pre operational
The device is in the “Pre operational” state
Single flash
Stopped
The device is in the “Stopped” state
On
Operational
The device is in the “Operational” state
Error LED
(ERR)
State
Description