Controller functions
Page 50
RES-440
Version 1
10.7
Temperature setting (set point selection)
The heatsealing temperature can be set on the RES-440 controller by means of the setting in menu step 101 [1].
The maximum value of the setting range is limited either by the maximum value specified with
step 206 [23] in the Configuration menu or by the heatsealing band type/temperature range set with
step 205 [22].
The set point that is selected for the heatsealing temperature must be greater than 40°C. If not, the heatsealing
band will not be heated up when the "START" signal is activated or the "HAND" key is pressed.
The set heatsealing temperature is displayed in the main menu once it has been entered.
• Output 1 is energized if the actual value is inside
the specified temperature tolerance band
(steps 207, 208). The relay remains energized at
the end of the heatsealing cycle and is not deen-
ergized again until the next "START" signal is
activated.
"Output 1" active if Tact =
Tset, with latch function
Time control ON:
• Output 1 is not activated
"Output 1" OFF
• Output 1 is energized if the start signal is
present. The relay is deenergized at the end of
the cooling phase.
"Output 1" active with
START signal
• Output 1 is energized when the actual value
reaches 95% of the set point. The relay is deen-
ergized at the end of the cooling phase.
"Output 1" active when
temperature reached
• Output 1 is energized at the end of the heating
phase and deenergized again at the end of the
cooling phase.
(This setting is possible as of software revision
010)
"Output 1" active during
cooling phase
• Output 1 is energized for up to 0.5 seconds at
the end of the cooling phase (momentary
impulse). The length of the momentary impulse
can be shortened by applying the "START"
signal (during the impulse).
"Output 1" generates end-
of-cycle impulse
• Output 1 is energized if the actual value is inside
the specified temperature tolerance band
(steps 207, 208).
"Output 1" active if Tact =
Tset
• Output 1 is energized if the actual value is inside
the specified temperature tolerance band
(steps 207, 208). The relay remains energized at
the end of the heatsealing cycle and is not deen-
ergized again until the next "START" signal is
activated.
"Output 1" active if Tact =
Tset, with latch function
225
Temperature unit
Unit for temperature display and input values
Celsius
Fahrenheit
No.
Name
Description
Setting range
!