Installation
Page 18
RES-430
Version 1
8.4
Wiring diagram with relay K1 (standard)
11
21
19
20
15
16
17
18
22
23
24
25
26
27
10
13
14
12
3
2
1
4
4
5
5
6
6
7
7
8
8
9
9
LINE
RES-430
START
K1
2x 47nF/560R
IMPORTANT:
If only ONE heatsealing band is used,
output terminals 7+8 must be jumped
with a high current cable in order to
avoid malfunctions or damage of the
controller. Step 240 in the Configuration
menu must be set to “Double” for this
purpose.
Band 1
Band 2
Heatsealing band
Load cell
interface
and
temperature
sensor
FOOT SWITCH
Main switch
Impulse
transformer
ANALOG
OUTPUT
(ACTUAL
temperature
of heatsealing
band)
+0...10VDC
GND/
Earth
Over-current protection
Double-pole circuit breaker
or fuse
(--> ROPEX Application report)
Short-circuit protection only.
RES-430 controller
not protected.