Controller functions
Version 1
RES-408
Page 47
11.13 Measuring impulse duration (as of June 2006)
The length of the measuring impulses generated by the controller can be set with this parameter. It may be nec-
essary to set a measuring impulse that is longer than the default 1.7ms for certain applications (
ROPEX Appli-
cation Report).
This parameter can only be set in the ROPEX visualization software (
interface / visualization software (as of June 2006)" on page 51).
11.14 Automatic phase compensation (AUTOCOMP) (as of June 2006)
It may be necessary to compensate the phase angle displacement between the U
R
and I
R
measuring signals in
certain heatsealing applications (
ROPEX Application Report). The "AUTOCOMP" function is provided for this
purpose. The following settings are possible:
1.
„OFF" (Factory settings)
The „AUTOCOMP“ function is deactivated.
2.
„ON“
The „AUTOCOMP“ function is activated by pressing the "ENTER" key after the "AUTOCAL" function has been
successfully executed (
section 11.8 "Automatic zero calibration (AUTOCAL)" on page 40). The interval after
the end of the "AUTOCAL" function must be less than 2.0s ("AP" appears on the terminal display during this
time and the three decimal points light up). The "AUTOCOMP" function only takes around 2.0s ("AP" appears
on the terminal display and the three decimal points light up consecutively).
If the interval following a successful "AUTOCAL" function is longer than 2.0s, the display returns to the home
position without executing the „AUTOCOMP“ function.
!
Function
"ENTER" key
pressed
"AC"
t
t
0
0
AUTOCAL
lit
t
OFF
<2.0s
AUTOCOMP
"AUTOCAL"
t
OFF
LED
lit
"OUTPUT"
LED
"AP"