Controller functions
Page 24
RES-401
Version 1
• By means of a control contact at terminals 15+18
The "START" signal is disabled as long as the AUTOCAL function is executing(As of October 2005: "AUTOCAL"
LED lit, "HEAT" LED blinks).
The terminals 15+18 are not potenial-free and might have the potential of the secondary voltage of
the impulse transformer.
For the terminals of the control contact touch voltage protection must be installed.
External grounding is not allowed. If this warning is ignored, the controller will be damaged by frame
currents.
The set point that is selected for the heatsealing temperature must be greater than 40°C. If not, the heatsealing
band will not be heated up (as of October 2005: "HEAT" LED blinks).
6.6
Diagnostic interface/visualization software (as of October 2005)
An interface with a 6-pole Modular Jack (RJ-12) is provided for system diagnostics and process visualization. This
interface allows a data connection to be set up to the ROPEX visualization software using the ROPEX communi-
cation interface CI-USB-1.
Only a ROPEX comunication interface is allowed to be connected to the diagnostic interface.
Connecting another device (e.g. a telephone cable) could result in malfunctions or damage to the
controller.
The ROPEX visualization software is described in a separate document.