Page 27
Meter Part
Configuration section
Address
Attribute
Measurement
Format
Default
Descriptions
40051
R/W
Communication ID
UINT16 1
1 - 247
40052
R/W
Wiring mode
UINT16 2 = 3P4W
0 = 3P3W, Open delta
1 = 3P3W, Wye
2 = 3P4W
40053
R/W
PT ratio
UINT16 10
0 - 19999
PT ratio value
= PT primary/ PT secondary
PT ratio = PT ratio value * 0.1
40054
R/W
CT ratio
UINT16 10
0 - 5000
CT ratio
= CT primary/ CT secondary
40055
R/W
Protocol
UINT16 1 = Modbus RTU
0 = Rootech[manufacturer]
1 = Modbus RTU
40056
R/W
Baud rate
UINT16 3 = 9600bps
0 = 1200bps
1 = 2400bps
2 = 4800bps
3 = 9600bps
4 = 19200bps
5 = 38400bps
40057
R/W
Parity bit
UINT16 2 = Even parity
0 = None parity
1 = Odd parity
2 = Even parity
40058
R/W
Stop bit
UINT16 0 = 1 stop bit
0 = 1 stop bit
1 = 2 stop bits
40059
R
Reserved
UINT16
40060
R
Reserved
UINT16
40061
R
Reserved
UINT16
40062
R/W
Reactive (Q) calculation
method
†
UINT16 0 = Method 1
0 = Method 1
1 = Method 2
40063
R/W
Demand time[Minute]
UINT16 15
1 - 60
40064
R
Reserved
UINT16
40065
R
Frequency
UINT16 0 = 60Hz
0 = 60Hz
1 = 50Hz
40066
R
Reserved
UINT16
•••
Invalid
UINT16
•••
40100
Invalid
UINT16
†
R
efer to “Accura 7500 User Manual” for detailed information on the method.
Measurement section
Address
Attribute
Measurement
Format
Scale
†
Descriptions
40101
R
Voltage a
UINT16
VSA[40109]
40102
R
Voltage b
UINT16
VSA[40109]
40103
R
Voltage c
UINT16
VSA[40109]