Page 22
Function 06: Write a Single Register to Meter
To write data to a single register, a Master should send the slave device a Write Single Register to
Meter request packet via
Function 06 code
.
Request
Slave
Function
Starting Address
Data Word
Error Check
06
1 byte
1 byte
2 bytes
2 bytes
2 bytes
Example]
Writes data[78hex] to the PT ratio [address 40053] of the relay 1.
Slave address = 1, starting address = 34, data word = 78, crc high =C8, crc low = 26
Slave
Function
Starting Address
Data Word
Error Check
01
06
00
34
00
78
C8
26
Response
In addition to the response to Function 06 command, the relay re-sends the request packet.
Example]
The response to the above request packet is as follows.
Slave
Function
Starting Address
Data Word
Error Check
01
06
00
34
00
78
C8
26
Function 16: Write Multiple Registers to Meter
Function 16[decimal] indicates the Request/Response format through which data is written to
multiple registers of the relay. [Note: the decimal number 16 is converted to the hexadecimal
number 10].
Request
Slave
Function
Starting Address
Word Count
Byte Count
10
1 byte
1 byte
2 bytes
2 bytes
1 byte
Data Word 1
---
---
---
Data Word N
Error Check
---
---
---
2 bytes
---
---
---
2 bytes
2 bytes