Chapter 2 Accura 2350-DO Operation/Setup
Accura 2350-DO User Guide
Page 18
ⓒ
2018 Rootech Inc. All Rights Reserved
Setup Mode
Each time the SET button is short pressed, the next setup menu is selected.
ID Setup
Output Control of
Channel 1
Output Control of
Channel 2
Channels
3-7
Output Control
of Channel 8
Note
If there is no button operation for 10 seconds on the setup screen, the screen automatically returns to
the display screen.
ID Setup
Setup Range
ID [d][d]
1
Default 255
Accura 2350 ID
2
Setup range: 0 - 39
1. d
→
decimal number.
2. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2350
modules as a factory default value.
Module ID
ID
Description
Communication ID ID 0 - 39
ID of the Accura 2350 module that enables communication
Conflict ID
Redundant IDs
There are more than 2 identical IDs. communication unavailable
Standby ID
ID 255
Module ID for checking connection status, communication unavailable
Output Control Setup for Channels [Ct
→
Control]
-
Setup Range
0 [
numeric
value
]
[default]
Outputs the command to
open the contact
Polarity=0 [Normal] status
1 [
numeric
value
]
Outputs the command to
close the contact
0 [
numeric
value
]
Outputs the command to
close the contact
Polarity=1 [Reverse] status
1 [
numeric
value
]
Outputs the command to
open the contact
Channel control commands can be issued via Modbus communication. Refer to
「
Accura 2300[S]/2350
Communication User Guide
」
for details on controls via communication.