Accura 2300S/2350-1P3FSC User Guide
Chapter 4 Accura 2300S Operation/Setup
ⓒ
2015 Rootech Inc. All Rights Reserved
Page 101
Voltage Swell End Threshold
The swell end threshold is configured as a percentage of the reference voltage. A swell event ends
when the measured voltage value drops back below the end threshold. You can set a hysteresis value
between the start and the end thresholds to prevent multiple events from occurring during a short
period of time, and the minimum hysteresis value is 1 %. In other words, the end threshold can be set
to a value at least 1 % less than the start threshold. If the start threshold is set to a value less than the
end threshold, the end threshold is automatically reset to a value 1 % less than the start threshold.
Setup Range
Description
101.0 - 998.0 %
(default 108.0 %)
Percentage of the reference voltage
Swell End Threshold Display
V
L-N
(Line-to-neutral)
3P4W/1P3W/1P2W connection
V
L-L
(Line-to-line)
3P3W connection
[d][d][d].[d]
1
V/kV
Swell end threshold
1. d
→
decimal
Fig 4.24 Swell Event Setup(3-phase 4-wire)
Reference voltage: set to 380 V Line-
to-line
(converted to the reference voltage:
line-to-neutral)
Fig 4.25 Swell Event Setup(3-phase 3-wire)
Reference voltage: set to 380 V Line-
to-line