4.2 Bus connection to Modbus master devices  

 

4.2.1 Communication within Modbus master/slave systems 

 
For communication between a controller (DDC or PLC) and the romutec® RCG32-Bridge devices, it is 
necessary to configure an TCP interface of the controller as Modbus master.  
 
To communicate with a slave device connected to the bridge, you have to send the telegrams to the  
IP address of the romutec® RCG32-bridge devices. This telegram contains the request message 
which is needed for the slave device, including the unique slave ID. 
 
This is done with the programming software of the manufacturer of the controller.  
For questions, please consult the manual or contact the manufacturer of the controller. 
 
 

4.2.2 Terminal assignment of the Modbus RTU (RS485) port  

 
The terminal assignment for the bus connection of the romutec® RCG32-bridge to Modbus RTU slave 
devices is as follows: 
 

Type of Interface 

Function 

Terminal No. 

Modbus Slave 

 

RS485-1 

 

Rx-Tx (Net_B ) 
/Rx-/Tx (Net_A ) 
I-GND 

1.6 
1.5 
1.8 

Data+ (B) 

Data- (A) 

Bus-GND 

 

RS485-2 

 

Rx-Tx (Net_B) 
/Rx-/Tx (Net_A) 
GND = supply GND 

1.4 
1.3 
1.1 

Data+ (B) 

Data- (A) 

Bus-GND 

 
 
The bus interface of serial 1 is electrically isolated. The I-GND terminals must always be wired, 
whether with braided shield or individual strands, and connected to ground / earth potential. There is 
no internal connection between I-GND of serial 1 and the GND of the power supply. 
 

 

The terminal 1.7 is connected to the shield of the RJ45 Ethernet socket. To avoid any 
unwanted behaviour of the device, connect that terminal direcly to earth potential. 

 

 
 
 

4.2.3 Recommended cable types for bus wiring  

 
For a total length  

up to 100m:    

 

 

more than 100m:  

 

Cable type:  

 

LIYCY 1x2x0,5mm² shielded  

 

CYPIMF 1x2x0,5mm² shielded 

Line resistance:  

< 4,0Ω / 100m    

 

 

< 4,0Ω / 100m  

Capacitance:    

< 13.0nF / 100m  

 

 

< 6.0nF / 100m 

 
 
 

4.2.4 Modbus commands supported  

 
All Modbus commands (aka FC = Function Codes) are supported. 
There are no restrictions in the bridge. 
 
 

 

Содержание 00003192

Страница 1: ...anges Technical Documentation Instruction Manual Romutec Control Gateway 32 Modbus TCP to Modbus RTU Bridge for use in building automation and control systems with management and diagnostic web interface for DIN rail mounting romutec Steuer u Regelsysteme GmbH Jochsberger Straße 39 D 91592 Buch am Wald Phone 49 0 98 67 97 90 0 Fax 49 0 98 67 97 90 90 E Mail info romutec de ...

Страница 2: ... Safety information 4 3 System description 5 4 Configuration 6 4 1 Hardware 6 4 2 Bus connection to Modbus master devices 8 4 2 1 Communication within Modbus master slave systems 8 4 2 2 Terminal assignment of the Modbus RTU RS485 port 8 4 2 3 Recommended cable types for bus wiring 8 4 2 4 Modbus commands supported 8 4 3 Configuration via Web Interface 9 4 3 1 Starting the Web Interface 9 4 3 2 Wi...

Страница 3: ... Parity None Even Odd o Stoppbits 1 or 2 o Baudrate 50Bd to 500 000Bd WIFI in AP Mode WIFI in Station Mode Ethernet RJ45 24V AC DC power supply input 2 serial interfaces in bridge mode with different settings 255 Telegrams buffer dynamically allocated 1 1 Copyright and legal notice Copyright 2021 romutec Steuer u Regelsysteme GmbH All rights reserved Without the express written permission this man...

Страница 4: ...ters must be provided with all safety measures in order to comply with the required regulations and guidelines e g line filter etc Do not use the product near water or other liquids which can damage the electronic components The supply voltage must correspond to the information in the technical data The terminals of the device should only be wired by authorized and trained personnel Do not perform...

Страница 5: ...nected to a Modbus RTU network and works as master device The communication speed baud rate and also the serial config are set up in web interface The two serial interfaces can be set up via webserver with different settings depending baud rate format and parity These two serial interfaces are named with serial 1 and serial 2 The serial 1 interface is an isolated RS485 transceiver with the termina...

Страница 6: ...devices on the non isolated serial 2 side without a Repeater Address 0 is reserved for multicast the addresses 248 to 254 are reserved for bridge and similar infrastructure functions Installation and wiring Installation and wiring of the module will be done in the cabinet on the mounting plate Addressing Serial Interface All incoming Modbus TCP requests are sent out on both serial interfaces So yo...

Страница 7: ...of RCG32 The LED in this mode will blink slowly red first If you have set the WiFi credentials for station mode via webserver the RCG32 will search for an according WiFi network and connects to it If RCG32 has established a connection succesfully the status LED turns to shine steadily red else it will blink quickly red showing that the WiFi settings are incorrect or the wanted WiFi is not reachabl...

Страница 8: ...ort The terminal assignment for the bus connection of the romutec RCG32 bridge to Modbus RTU slave devices is as follows Type of Interface Function Terminal No Modbus Slave RS485 1 Rx Tx Net_B Rx Tx Net_A I GND 1 6 1 5 1 8 Data B Data A Bus GND RS485 2 Rx Tx Net_B Rx Tx Net_A GND supply GND 1 4 1 3 1 1 Data B Data A Bus GND The bus interface of serial 1 is electrically isolated The I GND terminals...

Страница 9: ...1592 Buch am Wald www romutec de Subject to technical changes 4 3 Configuration via Web Interface 4 3 1 Starting the Web Interface When starting the web interface you will see an overview like shown in this picture 4 3 2 WiFi Configuration The default password for first access is 01234567 It can be changed at any time ...

Страница 10: ...Page 10 of 11 Subject to modifications romutec Steuer und Regelsysteme GmbH Jochsberger Straße 39 D 91592 Buch am Wald www romutec de Subject to technical changes 4 3 3 Ethernet Configuration 4 3 4 Serial Configuration ...

Страница 11: ...Baud 460 800 Baud 500 000 Baud Serial port parameter settings 5N1 5N2 5E1 5E2 5O1 5O2 6N1 6N2 6E1 6E2 6O1 6O2 7N1 7N2 7E1 7E2 7O1 7O2 8N1 8N2 8E1 8E2 8O1 8O2 Network Interface WLAN RJ45 Bus cycle time individually depending on the baud rate and the number of data points that will be addressed Memory microPC internally Max number of write cycles Configuration settings such as inverting the inputs a...

Отзывы: