PS20 Operating Manual RevD.doc 

 

2016-10-20 

       

1

Power Supply  

Type PS20  

v3.2 Rev. D 

P

RODUCT 

D

ESCRIPTION 

 

The PS20 is dedicated for electronic equipment  which require 12VDC buffered supply 
source. Device consist of metal case with compartment for sealed lead-acid  battery, 
mains transformer and electronic circuit. PS20 may deliver up to 2A current without any 
time limit, it utilize DC/DC “switched mode” electronic circuit which offer high efficiency 
(reduced heating of electronic components). PS20 employs internal current limiting and 

short circuit protection which make it essentially indestructible. The reserve battery is 
connected to output terminals trough an ultra low-resistance MOS transistor, such a 
circuit architecture enables optimum performance during AC failure and during dynamic 
changes of load when excessive current consumption is required. PS20 charge battery 
with 

constant current-constant voltage

 method, this method of charging guaranties 

relatively quick and safe charging process. The initial charging current is factory set to 
~300mA, installer should be aware that with battery connected to PS the output current 
will be reduced to 1700mA. Depending on battery charging phase the output voltage of 
PS20 may vary from approx. 11.5 up to 13.8V level. When battery voltage drops below 
~10.0V level internal circuit disconnect it from load, battery is automatically reconnected 
when AC supply returns. Battery cut off circuit protect battery from deep discharge but 
the equipment connected to power supply from operation below 10.0V level which in 
many cases can lead to undefined system behavior. Battery is protected with 5A fuse 
which reduce maximum output current sourced from battery and electronic circuit 
against battery reverse connection. PS20 offer two output ports (Z1 and Z2 terminals). 
The nominal output voltage is factory set to 13.8V and should not be changed by user. 
PS20 is equipped with two LEDs, the red one (marked as 230VAC) signalize that AC 
power exists where the second one (marked as 12VDC) signalize that output voltage is 
available.  

O

PTIONAL 

A

LARM 

M

ODULE 

PSAM-1 

For more sophisticated installation electronic circuit of PS20 can be equipped with 
optional alarm module (PSAM-1). This module can be connected to PS20 circuit through 
dedicated connector (CON4) which is located on PS20 board. The main purpose of PSAM-
1 module is to signalize an alarm situation of power supply to external device or system. 
The PSAM-1 may operate in autonomic or networked mode. When set to autonomic 
mode it offer  three transistors outputs which are dedicated to signalize following 
situations: 

low battery 

battery failure 

AC lost 

Those outputs can be connected to external control panel, access controller or another 
control or signaling device which will warn authorized personnel.  
When PSAM-1 operates in networked mode it must be connected to PR series access 
controller (PR302/PR402 or PR302LCD) through Clock & Data interface. In this mode 
PSAM-1 module sends all messages about power supply condition direct to access 
controller. During 

networked

 mode PSAM-1 signalize the same alarm condition as during 

standalone mode and additionally delivers data about actual voltage level available on 
PS’s output terminals. 
 