MCX402-BRD Installation Manual.doc
2021-06-18
1/2
Roger Access Control System
MCX402-BRD Installation Manual
Firmware version: 1.1.0.302 and newer
Hardware version: 1.0
Document version: Rev. C
This document contains minimum information that is necessary for initial setup
and installation of the device. The detailed description of configuration
parameters and functionalities is specified in respective Operating Manual
available at
I
NTRODUCTION
The expander is designed to operate in RACS 5 system as peripheral device
connected to RS485 bus of MC16 access controller. Depending on uploaded
firmware the expander enables to control single door by MC16 controller using
two terminals with Wiegand interface or two PRT series terminals. MCX402-BRD
is installed in MCX402-1-KIT and MCX-402-2-KIT.
Factory new device is configured with default settings including ID=100 address.
Before connecting to MC16 controller, the device should be assigned with
unoccupied address in range of 100-115. Programming of other parameters
depends on the individual requirements and is not obligatory. Configuration of
the expander with RogerVDM requires RUD-1 interface.
C
ONFIGURATION WITH
R
OGER
VDM
P
ROGRAM
Fig. 1 Connection of the expander to RUD-1 interface
Programming procedure with RogerVDM software:
1. Connect the device to RUD-1 interface (fig. 1) and connect the RUD-1 to
computer’s USB port.
2. Start RogerVDM program, select
MCX v1.x
device, firmware version,
RS485
communication channel and serial port with RUD-1 interface.
3. Click
Connect,
the program will establish connection and will automatically
display
Configuration
tab.
4. Enter unoccupied RS485 address in range of 100-115, enable Wiegand or
PRT terminals, configure input types (e.g. NC for IN5 according to fig. 5) and
other settings according to requirements of specific installation.
5. Click
Send to Device
to update the configuration of device.
6. Optionally make a backup by clicking
Send to File…
and saving settings to
file on disk.
Note: Time to connect to the device in RogerVDM is 30 seconds from power up.
In case of timeout, a power reset should be performed just before the
connection.
M
ANUAL ADDRESSING
The RS485 address of expander configured with RogerVDM is a software
address. Alternatively hardware RS485 address can be configured with jumpers
and such address has higher priority than software address.
Fig. 2 Manual addressing of expander
Note: Each time the hardware RS485 address is modified the device must be
restarted
M
EMORY RESET
Memory reset procedure restores factory default settings including ID=100
software address.
Expander memory reset procedure:
1. Remove all connections from A, B, CLK and DTA terminals.
2. Place jumper on 64 contacts and restart device with RST button on device
board or by switching supply off and on.
3. Remove jumper from 64 contacts when LED STAT (red), LED OPN and LED
SYS are ON.
4. LED OPN and LED SYS will switch off and device shall restart automatically
with factory default settings.
F
IRMWARE UPDATE
Factory new expander is equipped with a firmware dedicated to Wiegand
readers. If the expander is to be operated with PRT readers then another
firmware must be uploaded. Such firmware is available at
Firmware update requires RogerISP program.
Expander firmware update procedure:
1. Connect the device to RUD-1 interface (fig. 1) and connect the RUD-1 to
computer’s USB port.
2. Place jumper on FDM contacts
3. Restart device with RST button on device board or by switching supply off
and on.
4. Start RogerISP software.
5. Select serial port emulated by RUD-1 interface and the option
USB-RS485
Converter
.
6. Select firmware file (*.hex), click
Program
and follow instructions on screen.
7. Once the firmware is uploaded remove the FDM jumper and restart the
device.
8. Start Memory reset procedure.
A
PPENDIX
Fig. 3 MCX402-BRD expander
Table 1. Screw terminals
Name
Description
BAT+, BAT-
Backup battery