MCT88M-IO Installation Manual   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2019-10-02 

 

1/2 

 

Roger Access Control System 

MCT88M-IO Installation Manual 

Firmware version: 1.0.2.97 and newer 

Document version: Rev. F 

 

 

This  document  contains  minimum  information  that  is  necessary  for  initial  setup 
and  installation  of  the  device.  The  detailed  description  of  configuration 
parameters  and  functionalities  is  specified  in  respective  Operating  manual 
available a

www.roger.pl

I

NTRODUCTION

 

The  terminal  is  designed  to  operate  in  RACS  5  system  as  peripheral  device 
connected to RS485 bus of MC16 access controller. Alternatively the device can 
communicate  with  virtual  controller  via  Ethernet  (LAN)  and  operate  as  PoS 
terminal or assets management terminal. Factory new terminal is configured with 
default settings including ID=100 address. Before connecting to MC16 controller, 
the  device  should  be  assigned  with  unoccupied  address  in  range  of  100-115. 
Programming of other parameters depends on the individual requirements and is 
not  obligatory.  Configuration  of  the  terminal  with  RogerVDM  requires  RUD-1 
interface. 

C

ONFIGURATION WITH 

R

OGER

VDM

 PROGRAM

 

 

Fig. 1 Connection of the terminal to RUD-1 interface for configuration 

Programming procedure with RogerVDM software: 

1.  Place jumper on MEM contacts (fig. 3). 
2.  Connect the device to RUD-1 interface according to fig. 1 and connect RUD-

1 to computer’s USB port. The terminal will display CONFIG MODE text and 
orange LED SYSTEM will pulsate. 

3.  Start RogerVDM  program, select 

MCT

 device, 

v1.0

 firmware version, 

RS485

 

communication channel and serial port with RUD-1 interface. 

4.  Click 

Connect,

  the  program  will  establish  connection  and  will  automatically 

display 

Configuration

 tab. 

5.  Select  RS485  communication  interface  and  specify  unoccupied  RS485 

address in range of 100-115 or select Ethernet communication interface and 
specify  IP  address.  Configure  other  low  level  configuration  parameters  as 
needed. 

6.  Click 

Send to Device

 to update the configuration of device. 

7.  Optionally  make  a  backup  by  clicking 

Send to File… 

and  saving  settings  to 

file on disk. 

8.  Remove  jumper  from  MEM  contacts  and  disconnect  device  from  RUD-1 

interface. 

Note: If the USB port does not offer enough current then supply the terminal from 
external 12VDC PSU min. 200mA power output. 
 
Note:  Do  not  read  any  cards  nor  press  keypad  when  device  is  configured  with 
RogerVDM. 

M

ANUAL ADDRESSING

 

Manual addressing procedure enables configuration of new RS485 address with 
all other settings unchanged. 

Manual addressing procedure: 

1.  Remove all connections from A and B lines. 
2.  Place jumper on MEM contacts (fig. 3). 
3.  Restart the device (switch power supply off and on). The terminal will display 

CONFIG MODE text and orange LED SYSTEM will pulsate. 

4.  Enter 3 digits of RS485 address in range of 100-115 with keypad. 
5.  Wait till device starts to emit continuous sound. 
6.  Remove jumper from MEM contacts and restart the device. 

M

EMORY RESET PROCEDURE

 

Memory  reset  procedure  resets  all  settings  to  factory  default  ones  including 
ID=100 address. 

Memory reset procedure: 

1.  Remove all connections from A and B lines. 
2.  Place jumper on MEM contacts (fig. 15). 
3.  Restart the device (switch power supply off and on). The terminal will display 

CONFIG MODE text and orange LED SYSTEM will pulsate. 

4.  Press [*] or read any MIFARE card 11 times. 
5.  Wait till device confirms reset with continuous sound. 
6.  Remove jumper from MEM contacts and restart the device. 

F

IRMWARE UPDATE

 

New  firmware  can  be  uploaded  to  the  terminal  by  means  of  included  memory 
card. The latest firmware file is available a

www.roger.pl

 
Firmware update procedure: 

1.  Disconnect power supply. 
2.  Press and remove memory card from socket (fig. 3). 
3.  Using  memory  card  reader,  copy  main  firmware  (*.frg)  to  the  card  and 

rename  it  as  FW.BUF.  Copy  additional  firmware  (*.cyacd)  for  keypad  and 
BLE and rename it as KBDFW.CYA. 

4.  Insert the card into socket. 
5.  Connect power supply and wait till device completes starting procedure. The 

progress of additional firmware uploading is shown on the display. 

6.  Disconnect power supply when additional firmware KBD is 100% uploaded. 
7.  Connect power supply and wait till device completes starting procedure. 
8.  Start RogerVDM and perform low level configuration. 

Note:  During  the  firmware  update  process, it is  necessary  to  ensure  continuous 
and  stable  power  supply  for  the  device.  If  interrupted  the  device  may  require 
repair by Roger. 

 

A

PPENDIX

 

 

Fig. 2 Enclosure disassembly 

 

Fig. 3 Service contact and memory card 

 
 
 