Roger MCT82M SERIES Скачать руководство пользователя страница 1

 

Roger Access Control System 

MCT82M and MCT84M Operating Manual 

Product version: 1.0 

Firmware version: 1.1.18 or newer 

Document version: Rev. D 

 

 

 
 
 
 
 
 
 
 
 
 
 

 

 
 
 

 

Содержание MCT82M SERIES

Страница 1: ...Roger Access Control System MCT82M and MCT84M Operating Manual Product version 1 0 Firmware version 1 1 18 or newer Document version Rev D...

Страница 2: ...uts 1 relay output RS485 interface Tamper protection Screw terminals not in BK versions only MCT84M series only IO versions Power supply The terminal requires power supply voltage in range of 11 15VDC...

Страница 3: ...range of 100 115 The bus topology can be freely arranged as star tree or any combination of them except for loop The matching resistors terminators connected at the ends of transmitting lines are not...

Страница 4: ...low level configuration VISO v2 or RogerVDM of the terminal it is possible configure if terminal distinguishes short and long key pressings Consequently each types of key press can be assigned with di...

Страница 5: ...ut internally connected to tamper contact Input types and electric parameters such as response time and parametric resistors are defined within low level configuration VISO v2 or RogerVDM Input functi...

Страница 6: ...ctor is internally connected to the terminal s input It does not require low level configuration or any additional installation arrangements but it is essential to mount front panel in such way as the...

Страница 7: ...on 12V 12VDC power supply GND Ground A RS485 bus line A B RS485 bus line B IN1 IN1 input line IN2 IN2 input line IN3 IN3 input line IO1 IO1 output line IO2 IO2 output line NC REL1 relay normally close...

Страница 8: ...MCT82M MCT84M Operating Manual doc 22 06 2021 8 18 Fig 5 MCT82M installation...

Страница 9: ...MCT82M MCT84M Operating Manual doc 22 06 2021 9 18 Fig 6 MCT84M installation...

Страница 10: ...must be connected with any wire Device can be cleaned by means of wet cloth and mild detergent without abrasive components In particular do not clean with alcohols solvents petrol disinfectants acids...

Страница 11: ...30 266 or newer 1 Connect the device to RUD 1 interface fig 9 and connect the RUD 1 to computer s USB port 2 Remove jumper from MEM contacts fig 4 if it is placed there 3 Restart the device switch pow...

Страница 12: ...efault value 100 RS485 communication timeout s Parameter defines delay after which device will signal lost communication with controller When set to 0 then signaling is disabled Range 0 64s Default va...

Страница 13: ...ad If the number of entered digits is lower than this parameter then it cannot be sent to controller when concluded with key When set to 0 then PINs are disabled Range 4 8 Default value 4 Max length o...

Страница 14: ...nt which corresponds to the device object It is later displayed in VISO program Serial card number CSN settings Serial number length CSNL B Parameter defines the number of bytes from serial card numbe...

Страница 15: ...start the device switch power supply off and on or short RST contacts for a moment and orange LED SYSTEM will pulsate 4 Enter 3 digits of RS485 address in range of 100 115 with keypad or with any MIFA...

Страница 16: ...ion The update requires connection to computer with RUD 1 interface and starting RogerVDM software The latest firmware file is available at www roger pl Firmware update procedure 1 Connect the reader...

Страница 17: ...o EN 50133 1 Class II indoor general conditions temperature 10 C to 50 C relative humidity 10 to 95 no condensation Dimensions H x W x D MCT82M series 85 x 85 x 22 37 mm MCT84M series 130 x 45 x 22 mm...

Страница 18: ...electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste...