Roger Access Control System 

MC16-RAW-KIT Installation Manual 

Firmware version: n/a 

Document version: Rev. A 

 

 

This  document  contains  minimum  information  that  is  necessary  for  initial  setup 
and  installation  of  the  kit.  The  detailed  description  of  configuration  parameters 
and  functionalities  of  all  components  is  specified  in  respective  Operating 
manuals available a

www.roger.pl

I

NTRODUCTION

 

MC16-RAW-KIT  is  designed  to  control  from  one  to  sixteen  doors  in  RACS  5 
system.  Doors  can  be  read-in  or  read-in/out  type  when  equipped  with  MCT-IO 
series  readers  (RS485).  The  kit  includes  MC16-RAW  module  and  ME14-40VA 
metal  box  with  18VAC/40VA  transformer.  The  box  is  adapted  to  installation  of 
7Ah battery for emergency supply. 
In  case  of  MC16-RAW  module  it  is  required  to  order  and  upload  license,  which 
specifies its functionalities including the number of controlled doors. Alternatively, 
depending on the type of license the module can be operated not only as MC16-
PAC  door  access  controller  but  as  any  MC16  type  controller  (e.g.  MC16-HRC 
hotel  controller)  and  when  uploaded  with  new  firmware  the  module  can  also  be 
operated as expander (e.g. MCX16-AP). 

L

ICENSE UPLOAD

 

The  license  for  MC16-PAC  type  controller  is  uploaded  to  the  memory  card  of 
MC16-RAW module. 

License upload procedure: 

1.  Disconnect  power  supply,  press  memory  card  at  MC16-RAW  module  and 

remove it from the socket. 

2.  Insert  the  card  into  standard  reader  for  FLASH  memory  cards  and  connect 

the reader to computer’s USB port. 

3.  Copy ordered license.cfg file into memory card. 
4.  Insert memory card into socket of MC16-RAW module. 
5.  After  restoring  power  supply,  the  module  will  work  as  controller  with 

properties defined by its license. 

Note: The MC16 without license or with invalid license is not operated in RACS 5 
system. 

C

ONFIGURATION WITH 

R

OGER

VDM

 PROGRAM

 

Low  level  configuration  with  RogerVDM  software  mainly  concerns  MC16 
controller.  Additionally  it  is  necessary  to  define  individual  addresses  for  MCT 
series readers according to their installation manuals. 

MC16 programming procedure with RogerVDM software: 

1.  Connect the controller to Ethernet network and define the IP address of your 

computer  in  the  same  subnetwork  as  the  controller  with  192.168.0.213 
default IP address. 

2.  Start  RogerVDM  program,  select 

MC16  v1.x

  device,  the  latest  firmware 

version and 

Ethernet

 communication channel. 

3.  Select from the list or enter manually the IP address of controller, enter 1234 

communication key and start the connection with the controller. 

4.  In the top menu select 

Tools

 and then 

Set communication key

 to define your 

own password for the controller. 

5.  In the main window specify your own IP address of the controller. 
6.  Optionally  enter  comments  for  controller  and  its  object  to  facilitate  their 

identification during further configuration of the system. 

7.  Optionally backup settings clicking 

Send to File…

 

8.  Click 

Send to Device

 to update the configuration of controller and disconnect 

by selection of 

Device

 in the top menu and then 

Disconnect

M

EMORY RESET

 

Memory  reset  procedure  resets  all  settings  to  default  ones  and  results  in 
192.168.0.213 IP address and empty communication key. 

MC16 memory reset procedure: 

1.  Disconnect power supply 
2.  Short CLK and IN4 lines. 
3.  Restore power supply, all LEDs will flash and wait min. 6s. 
4.  Remove connection between CLK and IN4 lines, LEDs will stop pulsating and 

LED2 will be on. 

5.  Wait approx. 1.5 min till LED5+LED6+LED7+LED8 are pulsating. 
6.  Restart the controller (switch power supply off and on) 
7.  Start RogerVDM and make low level configuration. 

F

IRMWARE UPDATE

 

New  firmware  can  be  uploaded  to  the  controller  with  RogerVDM  software.  The 
latest firmware file is available a

www.roger.pl

MC16 firmware update procedure: 

1.  Connect with the controller using RogerVDM software. 
2.  Backup settings by clicking 

Send to 

File…

 

3.  In the top menu select 

Tools

 and then 

Update firmware

4.  Select firmware file and then click 

Update

5.  After firmware update wait till LED8 is pulsating. 
6.  Make or restore low level configuration in RogerVDM software. 

Note: During the firmware update process, it is necessary  to ensure continuous 
and  stable  power  supply  for  the  device.  If  interrupted,  the  device  may  require 
repair by Roger. 

P

OWER SUPPLY

 

The kit is supplied from 18VAC/40VA transformer. The metal box offers space for 
installation of typical  7Ah backup battery  which is connected to BAT+ and BAT- 
terminals of MC16 module. 
 

 

Fig. 1 MC16-RAW-KIT 

 

The installation can be done only by qualified person with all 
necessary certificates concerning connection and maintenance 
of 230VAC and low voltage networks. 

 

Prior to starting the installation it is necessary to ensure that 
230 VAC circuit is disconnected. All works inside the box must 
be carried out with 230VAC supply voltage disconnected. 

 

It is forbidden to use the kit without properly executed and 
operational earthing system. 

T

AMPER DETECTOR

 

The metal box is  equipped  with  door  contact  which  can be connected to  one of 
the  inputs  (e.g.  IN8)  and  GND  terminal  of  the  controller.  The  anti-sabotage 
function  can  be  assigned  to  the  input  within  high  level  configuration  of  the 
system. 

A

PPENDIX

 

Table 1. MC16 screw terminals 

Name 

Description 

BAT+, BAT- 

Backup battery 

AC, AC 

18VAC input power supply 

AUX-, AUX+ 

12VDC/1.0 output power supply (for door lock) 

TML-, TML+ 

12VDC/0.2A output power supply (for readers) 

IN1-IN8 

Input lines 

GND 

Ground 

OUT1-OUT6 

15VDC/150mA transistor output lines 

A1,B1 

RS485 bus 

CLK, DTA 

RACS CLK/DTA bus 

A2,B2 

Not used 