3-54
Programming and Parameters
IN
PUTS &
OU
TPUTS (File J)
A
n
al
o
g
O
u
tp
ut
s
343
[Analog Out1 Hi]
Sets the analog output value when the
source value is at maximum.
Default:
Min/Max:
Units:
10.00 Volts
0.00/10.00 Volts
0.00/20.00 mA
0.01 Volt
0.01 mA
344
[Analog Out1 Lo]
Sets the analog output value when the
source value is at minimum.
Default:
Min/Max:
Units:
0.00 Volts
0.00/10.00 Volts
0.00/20.00 mA
0.01 Volt
0.01 mA
354
[Anlg Out1 Scale]
Sets the high value for the range of analog
out scale. Entering 0.0 will disable this
scale and max scale will be used.
Example: If [Analog Out Sel] =
“Commanded Trq,” a value of 150 = 150%
scale in place of the default 800%.
Default:
Min/Max:
Units:
0.0
[Analog Out1 Sel]
0.01
377
[Anlg Out1 Setpt]
Controls the analog output value from a
communication device.
Example
Set [Data In A1] to “377” which will be the
value from the communication device.
Default:
Min/Max:
Units:
0.00 Volts
0.00/10.00 Volts
0.00/20.00 mA
0.01 Volt
0.01 mA
Fi
le J
Gr
oup
No.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Relate
d
E C
E C
E C
E C
E C
E C
E C
E C