Configure Switch Features
Chapter 7
Table 44 - Config DLR Fields
Field
Description
DLR Ring ID
(Stratix 5400 switches). Choose the ring number to configure:
• Ring 1
• Ring 2
• Ring 3
Mode
Choose one of these modes:
• Disabled—The DLR feature is disabled on the switch.
• Node—The switch is a ring node.
• Supervisor—The switch is a ring supervisor.
Default: Disabled
Port1
Choose a ring port. By default, if the switch is the ring supervisor, port 1 is node 1 on the ring, and port 2 is blocked.
Port2
Choose a ring port.
Supervisor Settings
Role (Precedence)
Choose a role to assign to the ring supervisor that corresponds to a predefined precedence value. The switch transmits the precedence value in beacon
frames and uses it to determine the active ring supervisor when multiple supervisors are configured. A higher value means higher precedence. When two
DLR supervisors have the same precedence, the device with the numerically highest MAC address becomes the active supervisor.
Valid values:
• None—0
• Primary—255
• Backup 1—100
• Backup 2—90
• Backup 3—80
• Custom—Type a value from 0…255
Beacon Interval
Type an interval for the supervisor to transmit beacon frames.
Valid values: 200…100,000 μs
Default: 400 μs.
Beacon Timeout
Type the amount of time ring nodes wait before timing out in the absence of received beacon messages.
Valid values: 200…500,000 μs
Default: 1960 μs
DLR Vlan Id
Type the VLAN ID for sending DLR protocol management frames.
Valid values: 0…4095
Default: 0 (no VLAN ID is used)
IMPORTANT:
DLR ports function only as access ports and not trunk ports.
Redundant Gateway Settings
Enable Redundant
Gateway
Check the checkbox to enable the configuration of redundant gateways. The configuration fields are available only after you enable the feature.
Default: Disabled
Role (Precedence)
Choose a role to assign to the redundant gateway that corresponds to a predefined precedence value. The switch transmits the precedence value is
advertise messages and is used to select the redundant gateway when multiple redundant gateways are configured. A higher value means higher
precedence. When two DLR redundant gateways have the same precedence, the device with the numerically highest MAC address will become the
redundant gateway.
Valid values:
• None—0
• Primary—255
• Backup 1—100
• Backup 2—90
• Backup 3—80
• Custom—Type a value from 0…255
Advertise Interval
Type the time interval for the gateway to transmit advertise messages.
Valid values: 200…100,000 μs
Default: 2000 μs
Содержание ArmorStratix 5700 series
Страница 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Страница 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Страница 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Страница 156: ...156 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 5 Install Stratix 5700 Switches Notes...
Страница 370: ...370 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 7 Configure Switch Features...
Страница 407: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 407 Monitor the Switch Chapter 8...
Страница 409: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 409 Monitor the Switch Chapter 8...
Страница 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Страница 494: ...494 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix B Port Assignments for CIP Data Notes...
Страница 540: ...540 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix D Cables and Connectors Notes...
Страница 547: ......