Configure Switch Features
Chapter 7
Overview
A DLR network is a single-fault-tolerant ring network that is intended for the
interconnection of automation devices without the need for more switches.
The ring topology offers these advantages:
• Media redundancy
• Fast-network fault detection and reconfiguration
• Resiliency of a single-fault-tolerant network
• Easy implementation without more hardware requirements
One DLR network can support as many as 50 nodes. A DLR network supports
copper connections (maximum of 100 m), fiber-optic connections (maximum
of 2 km), or a mix of copper and fiber.
Figure 12 - Example Device-level Ring Topology
Figure 13 - A DLR network includes the following nodes.
IMPORTANT
This section summarizes a DLR network. To plan, configure, and monitor
DLR networks, see EtherNet/IP Embedded Switch Technology Application
Guide, publication
.
Com
IN2
Ref
IN1
Alarm
IN1 IN2 OUT
DC+
Pwr A
Express
Setup
C
o
nsole
DC-
DC+
Pwr B
Esc
Sel
1783-ETAP
1783-ETAP
1783-ETAP
Stratix 5700 Switch
1756-EN2TR
1756 I/O Modules
1734-AENTR
1734 I/O Modules
1738-AENTR
1738 I/O Modules
1769-AENTR
1769 I/O Modules
To the Rest of the Network
PowerFlex® 525 Drive
IMPORTANT
Stratix 5700 and ArmorStratix 5700 switches support only one ring per
switch.
Stratix 5400 switches support as many as three rings per switch.
Содержание ArmorStratix 5700 series
Страница 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Страница 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Страница 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Страница 156: ...156 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 5 Install Stratix 5700 Switches Notes...
Страница 370: ...370 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 7 Configure Switch Features...
Страница 407: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 407 Monitor the Switch Chapter 8...
Страница 409: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 409 Monitor the Switch Chapter 8...
Страница 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Страница 494: ...494 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix B Port Assignments for CIP Data Notes...
Страница 540: ...540 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix D Cables and Connectors Notes...
Страница 547: ......