Install Stratix 5700 Switches
Chapter 5
3. After successfully running this test, do the following:
a. Turn off power to the switch.
b. Disconnect the cables.
c. Decide where you want to install the switch
Mount the Switch
on a DIN Rail
The switch ships with a spring-loaded latch on the rear panel for mounting on
a DIN rail.
WARNING:
If you connect or disconnect console port cables with power
applied to this module or any device on the network, an electrical arc can
occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING:
Do not use the USB-mini console port in hazardous locations.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
ATTENTION:
This equipment is supplied as open type equipment. It must be
mounted within an enclosure suitably designed for those specific
environmental conditions and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The interior of the enclosure
must be accessible only by using a tool.
The enclosure must meet IP 54 or NEMA type 4 minimum enclosure rating
standards.
ATTENTION:
To prevent the switch from overheating, observe these
minimum clearances:
• Top and bottom: 50.8 mm (2.0 in.)
• Exposed side (not connected to the module): 50.8 mm (2.0 in.)
• Front: 50.8 mm (2.0 in.)
Содержание ArmorStratix 5700 series
Страница 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Страница 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Страница 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Страница 156: ...156 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 5 Install Stratix 5700 Switches Notes...
Страница 370: ...370 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 7 Configure Switch Features...
Страница 407: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 407 Monitor the Switch Chapter 8...
Страница 409: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 409 Monitor the Switch Chapter 8...
Страница 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Страница 494: ...494 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix B Port Assignments for CIP Data Notes...
Страница 540: ...540 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix D Cables and Connectors Notes...
Страница 547: ......