Rockwell Automation Trusted T823 Series Скачать руководство пользователя страница 1

PD-T823X 

Trusted 

Rockwell Automation Publication PD-T823X 

Issue 11 

Trusted Power System 

Product Overview 

The Trusted® Power System is a high density flexible power supply designed to convert main line 

voltages of either 110 Vac or 240 Vac. Outputs are either 24 Vdc for Trusted product or 28 Vdc 

adjustable field power. 
The Trusted Power System consists of a 1U Power Shelf with mechanical support, containing up to 

three 750 W Power Packs. The Power Packs load share in configurations using one or more Power 

Shelves. Each Power Pack has an individual supply connection via a mechanically retained IEC 60320 

type connector. Each Power Shelf can supply 2250 W of power or 1500 W with n+1 redundancy 

from a single source. Multiple units can be connected for further capacity or redundancy 

requirements. 
Diagnostic information of Power Pack status is provided via the Power Port, which connects to the 

rear of the Power Shelf. This device monitors input and output conditions and reports out of range 

faults and over-temperature/fan failure using relay contacts. The Power Port also allows connection 

of the optional rack mounted Power Controller for live configuration, of output voltage and current, 

monitoring up to 12 Power Packs in 4 Power Shelves. 

Features: 

 

Redundant and N+1 configurations. 

 

Hot replaceable Power Packs. 

 

Current sharing. 

 

Current limiting. 

 

Power factor correction. 

 

Diagnostic contacts. 

 

Configurable output voltage. 

 

Input/output fail diagnostics per power pack. 

 

 

Содержание Trusted T823 Series

Страница 1: ...Shelf can supply 2250 W of power or 1500 W with n 1 redundancy from a single source Multiple units can be connected for further capacity or redundancy requirements Diagnostic information of Power Pac...

Страница 2: ...Trusted PD T823X Rockwell Automation Publication PD T823X Issue 11 Page intentionally left blank...

Страница 3: ...ormation available at the time of its publication The document contents are subject to change from time to time The latest versions of the manuals are available at the Rockwell Automation Literature L...

Страница 4: ...tion PD T823X DOCUMENTATION FEEDBACK Your comments help us to write better user documentation If you discover an error or have a suggestion on how to make this publication better send your comment to...

Страница 5: ...explosion in a hazardous environment which can cause injury or death property damage or economic loss ATTENTION Identifies information about practices or circumstances that can cause injury or death C...

Страница 6: ...te MAINTENANCE Maintenance must be carried out only by qualified personnel Failure to follow these instructions may result in personal injury CAUTION RADIO FREQUENCY INTERFERENCE Most electronic equip...

Страница 7: ...6 Fault relay details added 6 Apr 07 Inrush current details added 7 Nov 07 Current sharing 8 Sep 08 TC 323 clarification 9 Sep 08 Current sharing with low loads 10 Sep 15 Rebranded and reformatted wit...

Страница 8: ...PREFACE Trusted Power System vi Issue 11 Rockwell Automation Publication PD T823X Page intentionally left blank...

Страница 9: ...2 Overcurrent Protection 14 4 1 3 MCB Discrimination 14 4 2 Input Specification 15 4 3 Line Harmonics 15 4 4 Efficiency and Power Factor vs Input Voltage at Full Load 16 4 5 Output Specification 16 4...

Страница 10: ...Table of Contents Trusted Power System 2 Issue 11 Rockwell Automation Publication PD T823X 7 Power Shields 29 8 Power Shelf Interconnect 31 9 Power System Specification 33...

Страница 11: ...0 connector mains plugs and retaining clips T8231 Power Pack 24 Vdc 750 W universal input 24 Vdc out T8232 Power Pack 28 Vdc 750 W universal input 28 Vdc out T8233 Power Port Plug in diagnostic interf...

Страница 12: ...ct Range Trusted Power System 4 Issue 11 Rockwell Automation Publication PD T823X Figure 1 Front View Power Shelf with Power Packs Figure 2 Rear View Power Shelf Power Port uncovered and 4U Mounting B...

Страница 13: ...the Power Shelf The mounting bracket occupies 4U and can accommodate up to 4 Power Shelves The design is such that no space outside the 4U aperture is required When installed it is possible to remove...

Страница 14: ...ntacts When more than one Power Shelf is used Power Ports are linked via the CS terminal using a Power Shelf Interconnect cable to enable current sharing Spare slots in the Power Shelf are covered by...

Страница 15: ...d control features The Power Shelf can supply up to 1500 W of n 1 redundant power or up to 2250 W of total power depending on configuration of Power Packs Four stacked Power Shelves can provide up to...

Страница 16: ...A and B supplies or between two sets of Shelves which connect to separate busbars The supplies will attempt to share current between the two busbars which may damage the power packs and shelves sensin...

Страница 17: ...DC Fail_3 DC Fail signal of the third Power Pack 16 INT BUS Not used 17 AC Fail_1 AC Fail signal of the first Power Pack 18 On Off_3 Remote on off control for third Power Pack Not Used 19 SRTN Signal...

Страница 18: ...3 Power Shelf Specification Trusted Power System 10 Issue 11 Rockwell Automation Publication PD T823X Figure 5 Interface Connector...

Страница 19: ...Trusted Power System 3 Power Shelf Specification Rockwell Automation Publication PD T823X Issue 11 11 3 5 Stacked up Assembly Figure 6 4U Stacked up Assembly...

Страница 20: ...3 Power Shelf Specification Trusted Power System 12 Issue 11 Rockwell Automation Publication PD T823X Page intentionally left blank...

Страница 21: ...er Packs can be inserted and removed when live allowing hot swap of Power Packs see section 4 7 They are secured using a physical latch on the front of the Power Pack which is pushed up to release or...

Страница 22: ...rated to 18 75 V This derated voltage is on the limit of the Trusted System Modules specification Note This gradual increase is not typical of a system fault If 24 V is maintained over a rapid current...

Страница 23: ...r supplies in order to perform MCB discrimination studies 4 2 Input Specification Parameter Min Type Max Unit Condition Input Voltage 90 264 Vac Input Frequency 47 63 Hz Inrush Current peak per Pack 5...

Страница 24: ...and Power Factor vs Input Voltage at Full Load When using this table to calculate cable feed requirements allow at a minimum an extra 3 for variations between units Actual measured results will depend...

Страница 25: ...input on off or reinsertion Output Current Limit steady state 40A Adc Transient Response Voltage Range 2 2 25 step load transient with slew rate 0 1 A us within the range from 25 to 75 of full load Ac...

Страница 26: ...Sound Pressure Level at 1 m Relative Humidity non condensing 10 95 Altitude 60 3962 m Derated at 2 C 304 m above 2438 m Electro Static Discharge IEC 61000 4 2 Level 3 stand alone Electromagnetic Immu...

Страница 27: ...Trusted Power System 4 Power Pack Specifications Rockwell Automation Publication PD T823X Issue 11 19 Figure 9 Operation Derating Curve...

Страница 28: ...ckwell Automation Publication PD T823X 4 7 Power Pack Hot Replacement 1 Plug in slowly and smoothly 2 Make sure the first set of pins are contacted the AC OK LED will illuminate 3 Push fully home the...

Страница 29: ...nd miscellaneous electronic components The shape and size of the Power Port is shown in Figure 11 Figure 11 Power Port Outline Drawing The alarm contacts are made available on a connector for ease of...

Страница 30: ...low voltage electronics The 24 V is used to supply the relays and is connected through CON2 to power the optional Power Controller 5 2 2 DC Alarms CON1 is the 25 way D male interface to the Power She...

Страница 31: ...Off Low Open Open OFF Table 7 Alarm Conditions 5 2 4 Jumpers There are three jumpers J1 J2 and J3 J1 and J2 set the Power Shelf address lines for the I2C control bus With J1 and J2 fitted the Pack ad...

Страница 32: ...ower Shelf The pin out details are shown in Table 2 CON 2 is used to connect to other Power Shelves to current share or to connect to a Power Controller Pin Number Signal Name Description 1 2 3 4 ON S...

Страница 33: ...Connected Pins on CON 2 5 3 2 Pin out CON 3 Pin Description 1 24 V system supply 2 DCFAIL common 3 DCFAIL_3 4 DCFAIL_2 5 DCFAIL_1 6 0 V system supply return 7 ACFAIL_1 8 ACFAIL_2 9 ACFAIL_3 10 AC Fai...

Страница 34: ...Specifications Contact Form SPDT Resistive Load at 125 Vac 0 5 A at 24 Vdc 1 A Max Switching Power 62 5 VA 30 W Rated Voltage 3 Vdc to 24 Vdc Power Consumption 150 mW Mechanical Endurance 5 000 000 o...

Страница 35: ...ly regardless of its voltage setting when plugged in is adjusted via the I2C serial data bus to be within the current voltage sharing window of the power supply s analogue control circuitry The front...

Страница 36: ...Controller Outline Drawing 6 1 Power Up Sequence When a Power Controller is connected to more than one Power Shelf Power Shelves should have their supplies applied in turn e g power up first Shelf id...

Страница 37: ...Trusted Power System 7 Power Shields Rockwell Automation Publication PD T823X Issue 11 29 7 Power Shields If a Power Shelf is not fully populated Power Shields are used to cover unused spare slots...

Страница 38: ...7 Power Shields Trusted Power System 30 Issue 11 Rockwell Automation Publication PD T823X Page intentionally left blank...

Страница 39: ...ntroller The supplied ribbon cable has 5 connectors to allow the maximum of 4 Shelves and a Power Controller to be connected Do not connect the TC 323 cable between A and B supplies or between two set...

Страница 40: ...8 Power Shelf Interconnect Trusted Power System 32 Issue 11 Rockwell Automation Publication PD T823X Page intentionally left blank...

Страница 41: ...Pack Power Hold up Time 20 ms Operating Temperature 0 C to 60 C 32 F to 140 F Relative Humidity range operating storage transport 10 95 non condensing Environmental Specifications Refer to Document 55...

Отзывы: