C-28
EtherNet/IP Objects
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Host DPI Parameter Object
Class Code
To access Device parameters, use the DPI Parameter Object (Class
Code 0x93).
Instances
The number of instances depends on the number of parameters in the
device. The total number of parameters can be read in Instance 0,
Attribute 0.
Class Attributes
Hexadecimal
Decimal
0x9F
159
Instances (Hex.)
(Dec.)
Device
Example Description
0x0000 – 0x3FFF
0 – 16383
Reserved
16384
Class Attributes (Adapter)
0x4000 – 0x43FF
16384 – 17407
Adapter
16385
Adapter Parameter 1 Attributes
0x4400 – 0x47FF
17408 – 18431
Port 1
16386
Adapter Parameter 2 Attributes
0x4800 – 0x4BFF
18432 – 19455
Port 2
…
…
0x4C00 – 0x4FFF 19456 – 20479
Port 3
17408
Class Attributes (HIM)
0x5000 – 0x53FF
20480 – 21503
Port 4
17409
HIM Parameter 1 Attributes
0x5400 – 0x57FF
21504 – 22527
Port 5
17410
HIM Parameter 2 Attributes
0x5800 – 0x5BFF
22528 – 23551
Port 6
…
…
0x5C00 – 0x5FFF 23552 – 24575
Port 7
0x6000 – 0x63FF
24576 – 25599
Port 8
0x6400 – 0x67FF
25600 – 26623
Port 9
0x6800 – 0x6BFF
26624 – 27647
Port 10
0x6C00 – 0x6FFF 27648 – 28671
Port 11
0x7000 – 0x73FF
28672 – 29695
Port 12
0x7400 – 0x77FF
29696 – 30719
Port 13
0x7800 – 0x7BFF
30720 – 31743
Port 14
Attribute ID Access Rule Name
Data Type
Description
0
Get
Number of Instances
UINT
Number of parameters in the device
1
Set
Write Protect Password
UINT
0 = Password disabled
n = Password
2
Set
NVS Command Write
USINT
0 = No Operation
1 = Store values in active memory to NVS
2 = Load values in NVS to active memory
3 = Load default values to active memory
3
Get
NVS Parameter Value Checksum
UINT
Checksum of all parameter values in a user set in NVS
4
Get
NVS Link Value Checksum
UINT
Checksum of parameter links in a user set in NVS
5
Get
First Accessible Parameter
UINT
First parameter available if parameters are protected by
passwords. A “0” indicates all parameters are protected.
7
Get
Class Revision
UINT
2 = DPI
8
Get
First Parameter Processing Error
UINT
The first parameter that has been written with a value
outside of its range. A “0” indicates no errors.
9
Set
Link Command
USINT
0 = No Operation
1 = Clear All Parameter Links (This does not clear links
to function blocks.)
Содержание PowerFlex 755 Drive
Страница 1: ...USER MANUAL Firmware Version 1 xxx PowerFlex 755 Drive Embedded EtherNet IP Adapter...
Страница 152: ...7 6 Troubleshooting PowerFlex 755 Drive Embedded EtherNet IP Adapter User Manual Publication 750COM UM001A EN P Notes...
Страница 166: ...A 2 Specifications PowerFlex 755 Drive Embedded EtherNet IP Adapter User Manual Publication 750COM UM001A EN P Notes...
Страница 224: ...G 8 Glossary PowerFlex 755 Drive Embedded EtherNet IP Adapter User Manual Publication 750COM UM001A EN P Notes...
Страница 229: ...Index 5 PowerFlex 755 Drive Embedded EtherNet IP Adapter User Manual Publication 750COM UM001A EN P Notes...
Страница 230: ...Index 6 PowerFlex 755 Drive Embedded EtherNet IP Adapter User Manual Publication 750COM UM001A EN P Notes...
Страница 231: ......